5.3.4 Occupancy operation
Occupancy duration:
time while the last occupancy signal is considered valid.
Occupancy 1
st
action timeout:
if no valid occupancy signal is received during this time,
action 1 will be executed.
Occupancy 1
st
action:
occupancy action type:
-
APPLY_DELTA: it will apply an increment of temperature depending on the mode.
-
SWITCH_OFF: the AC unit will be switched OFF.
Occupancy 1
st
action delta heat:
if action 1 is configured as APPLY_DELTA, increment to
apply in heat mode.
Occupancy 1
st
action delta cool:
if action 1 is configured as APPLY_DELTA, increment to
apply in cool mode.
Occupancy 2
nd
action active:
if true, the 2
nd
action will be performed as well.
Occupancy 2
nd
action timeout:
if no valid occupancy signal is received during this time,
action 2 will be executed.
Occupancy 2
nd
action:
occupancy action type:
-
APPLY_DELTA: it will apply an increment of temperature depending on the mode.
-
SWITCH_OFF: the AC unit will be switched OFF.
Occupancy 2
nd
action delta heat:
if action 2 is configured as APPLY_DELTA, increment to
apply in heat mode.
Occupancy 2
nd
action delta cool:
if action 2 is configured as APPLY_DELTA, increment to
apply in cool mode.
Occupancy reload last value:
if true, previous ON/OFF state is restored when the room is
occupied.
Occupancy lock when unoccupied:
if true, ON/OFF state is forced to OFF while the room
is unoccupied.
5.3.5 Input operation
There are three configurable parameters per each input, so X is valid from 1 to 4 in the
following lines:
Input X inverted:
input X logic inversion, if true input X is inverted.
Input X function:
input X can be configured in order to behave as:
-
NONE: input X is only transmitted to EnOcean, with any other effect.
-
ON_OFF: input X is able to change the ON/OFF state of the AC unit.
-
WINDOW_CONTACT: input X is used as a window contact.
-
KEY_CARD: input X behaves as a key card reader.
-
OCCUPANCY: input X is used as an occupancy sensor.
Input X key card:
input X is transmitted to EnOcean as a key card, which means that just
one telegram will be sent per each change on the state of input X.