12.3 EEP: 07-10-03
ORG = 07 (4 BS)
FUNC = 10 (Room Operating Panel)
TYPE = 03 (Temperature Sensor, Set Point Control)
EEP for Room Operating Panel
–
Functions: Temperature Sensor, Set Point Control: With this EEP plus the already
existing EEP 07-20-11 and 07-20-10 all the information of AC indoor unit can be sent and received allowing a much
easier and complete control of these units.
Teach-In
The teach-in telegram has the same structure as a normal 4BS telegram.
See EnOcean Equipment Profiles (EEP) v2.1 and use the following structure.
DB_3.7 ... DB_3.2:
Function: same as teach-in telegram heating valve = 20
DB_3.2 ... DB_2.3:
Type: same as teach-in telegram actuator = 11
DB_2.2 ... DB_1.0:
Manufacturer: Intesis Software ID = 0x019
DB_0.7:
LRN TYPE = 0b1 (type 1 with profile, manufacturer Id)
DB_0.6:
EEP result; EEP supported = 0b1, EEP not supported = 0b0
DB_0.5:
LRN result; ID stored = 0b1, ID deleted (not stored) = 0b0
DB_0.4:
TA: teach-in answer = 0b1
DB_0.3:
LRN Learn button
0b0 Teach-in telegram
0b1 Data telegram
DB_0.2 ... DB_0.0:
Not used
DATA BYTES
DB_3
Not used
DB_2
Set Point
1
0 ... 255 Set Point (0 ... 40ºC)
DB_1
Temperature
2
255 ... 0 Temperature (0 ... 40ºC)
DB_0.7 ... DB_0.4
Not used
DB_0.3
Learn Button
0b0
Teach-in telegram
0b1
Data telegram
DB_0.2 ... DB_0.0
Not used
1
Scaling with values 0 ... 40 ºC only apply with profiles E and F.
2
While no sensor is linked to the IntesisBox
®
, a value of 0xFF will be sent indicating “no valid temperature”.