IntesisBox

 

is a registered trademark of Intesis Software SLU

 

 

  Occupancy 

Occupancy  function  is  used  to  determine  how  the  Air  Conditioner  unit  will  be  set  depending  on  the  presence  or 
absence of people in the room. Remember that the occupancy signal needs to be fed by an external sensor which 
indicates if there is presense or not (occupancy). This signal is processed directly in the IntesisBox and modifies 3 
parameters from the AC system: Setpoint, Mode and On/Off. 
 
 
In order to adjust the settings to the current mode (Heat or Cool), the gateway offers 6 different BACnet objects: 
 

 

OccupiedCoolSetPoint 

 

OccupiedHeatSetPoint 

 

UnoccupiedCoolSetPoint 

 

UnoccupiedHeatSetPoint 

 

OccupancyContinousCheck 

 

UnoccupiedDeadbandAction 
 
 
 
 
 
 
 
 
 
 
 

 
 

Occupancy/Unoccupancy  Cool  Setpoint  (OCS/UCS):

  Default  value  for  setpoint  temperature  to  be  set  when 

Occupancy/Unoccupancy  is  enabled  and  current  mode  is  cool.  UCS  must  always  be  greater  or  equal  to  OCS. 
Difference between OCS and OHS must be greater or equal to 2ºC/4ºF. 

 

Occupancy/Unoccupancy  Heat  Setpoint  (OHS/UHS):

  Default  value  for  setpoint  temperature  to  be  set  when 

Occupancy/Unoccupancy  is  enabled  and  current  mode  is  heat.  UHS  must  always  be  smaller  or  equal  to  OHS. 
Difference between OCS and OHS must be greater or equal to 2ºC/4ºF. 

 

Occupancy  Continous  check: 

This  checkbox  is  used  to  determine  if  the  gateway  will  check  the  occupancy 

conditions constantly (check) or not (unchecked) by default. That means that with the the checkbox active, conditions 
are checked on each change of the temperature too, while if unchecked, this is only checked when the occupancy 
status changes. 
 

Unoccupied Deadband Action: 

This determines the action to be taken while the ambient temperature is in between 

the deadband. If unchecked, indoor unit will turn off and if checked it will remain on.  
 
 
When 

occupancy mode is active 

(there is presence in the room), according to current room temperature, 

mode

setpoint

 and 

on/off 

will be set to: 

 

Condition 

Setpoint 

Mode 

On/Off 

Room temperature > OCS 

Current OCS value 

Cool 

On 

Room temperature < OHS 

Current OHS value 

Heat 

On 

OCS < Room temperature > OHS 

OCS/OHS depending on current mode  

(If Fan or Dry mode is active, no setpoint is sent) 

Current 
mode 

On 

 
 
When 

unoccupancy mode is active

 (there  is no presence in the room), according to current room temperature, 

mode

setpoint

 and 

on/off 

will be set to: 

Occupancy Cool SetPoint (OCS) 

Occupancy Heat SetPoint (OHS) 

Unoccupancy Cool SetPoint (UCS) 

Unoccupancy Heat SetPoint (UHS) 

Содержание MH-RC-BAC-1

Страница 1: ...sbishi Heavy Industries Air Conditioning Compatible with RAC Series FD Series KX6 and KXR6 VRF Series air conditioners commercialized by Mitsubishi Heavy Industries RAC Series require optional SC BIKN...

Страница 2: ...under a license agreement or nondisclosure agreement The software may be used only in accordance with the terms of those agreements No part of this publication may be reproduced stored in a retrieval...

Страница 3: ...d IntesisBox is a registered trademark of Intesis Software SLU Gateway for the integration of Mitsubishi Heavy Industries air conditioning units in BACnet enabled monitoring and control systems Compat...

Страница 4: ...ent Management BIBBs 10 Scheduling BIBBs 11 Trending BIBBs 11 Network Management BIBBs 11 Device Management BIBBs 12 4 Service Types 13 5 Objects 14 Supported Object Types 14 Member objects 15 5 2 1 T...

Страница 5: ...tPoint Analog Value Object Type 40 5 3 24 OccupiedHeatSetPoint Analog Value Object Type 41 5 3 25 UnoccupiedCoolSetPoint Analog Value Object Type 42 5 3 26 UnoccupiedHeatSetPoint Analog Value Object T...

Страница 6: ...utomation To do it so IntesisBox allows BACnet communication allowing polling or subscription requests COV IntesisBox makes available the Mitsubishi Heavy Industries air conditioning system indoor uni...

Страница 7: ...and its associated elements Element Max Notes Number of indoor units 1 Number of indoor units that can be controlled through IntesisBox Number of Objects 32 Number of Mitsubishi Heavy Industries AC si...

Страница 8: ...ties and functionalities as BACnet Objects BACnet Standardized Device Profile Annex L BACnet Operator Workstation B OWS BACnet Building Controller B BC BACnet Advanced Application Controller B AAC BAC...

Страница 9: ...ARCNET Ethernet Ethernet MS TP etc Annex H BACnet Tunneling Router over IP BACnet IP Broadcast Management Device BBMD Does the BBMD support registrations by Foreign Devices Yes No Character Sets Suppo...

Страница 10: ...B SubscribeCOV ConfirmedCOVNotification UnconfirmedCOVNotification DS COVP A Data Sharing COVP A SubscribeCOV ConfirmedCOVNotification UnconfirmedCOVNotification DS COVP B Data Sharing COVP B Subscri...

Страница 11: ...mated Trend Retrieval B ConfirmedEventNotification ReadRange BIBB Type Active BACnet Service Initiate Execute T VMT A Trending Viewing and Modifying Trends A ReadRange T VMT I B Trending Viewing and M...

Страница 12: ...sage B ConfirmedTextMessage UnconfirmedTextMessage DM TS A Device Management TimeSynchronization A TimeSynchronization DM TS B Device Management TimeSynchronization B TimeSynchronization DM UTC A Devi...

Страница 13: ...eadFile AtomicWriteFile Object Access Services AddListElement RemoveListElement CreateObject DeleteObject ReadProperty ReadPropertyConditional ReadPropertyMultiple ReadRange WriteProperty WritePropert...

Страница 14: ...rature_command Analog Value 2 OnTimeCounter OccupiedCoolSetPoint OccupiedHeatSetPoint UnoccupiedCoolSetPoint UnoccupiedHeatSetPoint Averaging 18 Binary Input 3 OnOff_status ErrorActive FIlterSign Bina...

Страница 15: ...f_command BO 0 Mode_status MI 0 Mode_command MO 0 SetPoint_status AI 0 SetPoint_command AO 0 FanSpeed_status MI 1 FanSpeed_command MO 1 AirDirectionUD_status MI 2 AirDirectionUD_command MO 2 RoomTempe...

Страница 16: ...more information 5 3 1 Mitsubishi Heavy Industries AC Gateway Device Object Type Property Identifier Property Datatype Value ASHRAE IBOX Object_Identifier BACnetObjectIdentifier Device 246000 R R Obj...

Страница 17: ...Unsigned 0 R R Configuration_Files BACnetArray N of BACnetObjectIdentifier O Last_Restore_Time BACnetTimeStamp O Backup_Failure_Timeout Unsigned16 O Active_COV_ Subscriptions List of BACnetCOVSubscrip...

Страница 18: ...ring O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 U...

Страница 19: ...FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Polarity BACnetPolarity NORMAL 0 R R Inactive_Tex...

Страница 20: ...O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of_Servic...

Страница 21: ...Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Number_Of_Sta...

Страница 22: ...ags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of_Service BOOLEAN F...

Страница 23: ...FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Update_Interval Unsigned O Units BACnetEngineeringUnits...

Страница 24: ...O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of_Servi...

Страница 25: ..._Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Number_Of_St...

Страница 26: ...cterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Ou...

Страница 27: ...CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEA...

Страница 28: ...ANALOG_INPUT 0 R R Present_Value REAL 10 50 R R Description CharacterString O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventStat...

Страница 29: ..._Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service...

Страница 30: ...racterString O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED...

Страница 31: ...Type MULTISTATE_INPUT 13 R R Present_Value Unsigned 1 92 R R Description CharacterString O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEv...

Страница 32: ..._Value State_Text 1 32 E30 63 E61 2 CommError 33 E31 64 E62 3 E1 34 E32 65 E63 4 E2 35 E33 66 E64 5 E3 36 E34 67 E65 6 E4 37 E35 68 E66 7 E5 38 E36 69 E67 8 E6 39 E37 70 E68 9 E7 40 E38 71 E69 10 E8 4...

Страница 33: ...haracterString O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTE...

Страница 34: ...ue REAL R R Description CharacterString O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACn...

Страница 35: ...E R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Polarity BACnetPolarity NORMAL 0 R R Inactive_Text Characte...

Страница 36: ...UE 2 R R Present_Value REAL 0 65535 R R Description CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetRelia...

Страница 37: ..._Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTH...

Страница 38: ...SE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Polarity BACnetPolarity NORMAL 0 R R Inactive_Text Charact...

Страница 39: ...String O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R...

Страница 40: ...32 C 60 90 F R R Description CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECT...

Страница 41: ...32 C 60 90 F R R Description CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECT...

Страница 42: ...16 32 C 60 90 F R R Description CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DET...

Страница 43: ...16 32 C 60 90 F R R Description CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DET...

Страница 44: ...racterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN F...

Страница 45: ...W W Description CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_O...

Страница 46: ...BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Inactive_Text Chara...

Страница 47: ...nt_Value REAL R R Description CharacterString O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliabilit...

Страница 48: ...cterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FAL...

Страница 49: ...RC as master its PCB switch must be set as Master and the MH RC BAC 1 must be configured as Slave If we want to use the RC as slave its PCB switch must be set as Slave and the MH RC BAC 1 must be con...

Страница 50: ...can be configured using SW2 DIP Switch Binary value b7 b0 Decimal value Switches 1 2 3 4 5 6 7 8 MAC address 0000000x 0 x 0 1000000x 1 x 1 0100000x 2 x 2 1100000x 3 x 3 1011111x 125 x 125 0111111x 126...

Страница 51: ...the configuration tool and select either DHCP or another static IP recommended that suits your integration project requirements Check section 7 5 for more information 6 3 1 BACnet Device Instance If t...

Страница 52: ...that gateway is working properly is to check physical connections 1 Make sure that the supplied cable is correctly connected between the AC unit and the gateway MH RC BAC 1 needs to be connected to th...

Страница 53: ...UHS Default value for setpoint temperature to be set when Occupancy Unoccupancy is enabled and current mode is heat UHS must always be smaller or equal to OHS Difference between OCS and OHS must be gr...

Страница 54: ...alue Heat On OCS Room temperature OHS UCS UHS depending on current mode If Fan or Dry mode is active no setpoint is sent Current mode On Deadband action 1 Off Deadband action 0 These checks will be do...

Страница 55: ...same network domain in order to connect The default IP is 192 168 100 246 7 5 1 Home Once you reach the page remember to login with your user and password To access the login site click on User or use...

Страница 56: ...s IP seetings and AC settings can be configured Each type of parameter is grouped in different blocks 7 5 3 Signals On this section a complete list of the available BACnet objects their type Object In...

Страница 57: ...of Intesis Software SLU When you click on Edit you will have the change of introducing a new value to be applied and also the priority NOTE If you want to relinquish the selected priority please use...

Страница 58: ...ded wires twisted or with ferrule 1 core 0 5 2 5mm2 2 cores 0 5 1 5mm2 3 cores not permitted Console Port Mini USB port for console usage Mounting Wall DIN rail EN60715 TH35 BACnet MS TP port 1 x EIA4...

Страница 59: ...by mixed setting method 14 16 E14 Communication error between master and slave indoor units 16 18 E16 Indoor fan motor anomaly 19 21 E19 Indoor unit operation check drain motor check setting error 28...

Страница 60: ...thermistor anomaly 56 58 E56 Power transistor temperature thermistor anomaly 57 59 E57 Insufficient in refrigerant amount or detection of service valve closure 58 60 E58 Anomalous compressor by loss o...

Отзывы: