5.3.5 Mode_command (Multistate Output Object Type)
It allows control over the
indoor unit’s mode.
Property Identifier
Property Datatype
Value
ASHRAE IBOX
Object_Identifier
BACnetObjectIdentifier
(Multi-state Output, 0)
R
R
Object_Name
CharacterString
“Mode_command”
R
R
Object_Type
BACnetObjectType
MULTISTATE_OUTPUT (14)
R
R
Present_Value
Unsigned
1 ~ 5
W
W
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Number_Of_States
Unsigned
5
R
R
State_Text
BACnetArray[N] of
CharacterString
Check Mode Command setting table below
O
R
Priority_Array
BACnetPriorityArray
BACnetPriorityArray
R
R
Relinquish_Default
Unsigned
1
R
R
Time_Delay
Unsigned
-
O
-
Notification_Class
Unsigned
-
O
-
Feedback_Value
Unsigned
-
O
-
Event_Enable
BACnetEventTransitionBits
-
O
-
Acked_Transitions
BACnetEventTransitionBits
-
O
-
Notify_Type
BACnetNotifyType
-
O
-
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
-
Profile_Name
CharacterString
-
O
-
Mode Command setting table
Mode commands can be set using the values in the following correspondence table.
Pesent_Value
Contents displayed in State_Text
1
Heat
2
Cool
3
Fan
4
Dry
5
Auto