5.3.12 RoomTemperature_status (Analog Input Object Type) 

 
It  indicates  the  room  temperature  from  the  sensor  in  the  indoor  unit.  Check  section 

¡Error!  No  se  encuentra  el 

origen de la referencia.

 for more information. 

 

Property Identifier 

Property Datatype 

Value 

ASHRAE  IBOX 

Object_Identifier

 

BACnetObjectIdentifier

 

(Analog Input, 1)

 

R

 

R

 

Object_Name

 

CharacterString

 

“RoomTemperature_status”

 

R

 

R

 

Object_Type

 

BACnetObjectType

 

ANALOG_INPUT (0)

 

R

 

R

 

Present_Value

 

REAL

 

-10

…50 

R

 

R

 

Description

 

CharacterString

 

-

 

O

 

-

 

Device_Type

 

CharacterString

 

O

 

-

 

Status_Flags

 

BACnetStatusFlags

 

{FALSE, FALSE/TRUE, FALSE, FALSE}

 

R

 

R

 

Event_State

 

BACnetEventState

 

STATE_NORMAL (0)

 

R

 

R

 

Reliability

 

BACnetReliability

 

NO_FAULT_DETECTED (0), 
UNRELIABLE_OTHER (7)

 

O

 

R

 

Out_Of_Service

 

BOOLEAN

 

FALSE/TRUE

 

R

 

R

 

Update_Interval

 

Unsigned

 

-

 

O

 

-

 

Units

 

BACnetEngineeringUnits

 

Degrees Celsius (62) 
Degrees Fahrenheit (64) 

R

 

R

 

Min_Pres_Value

 

REAL

 

-

 

O

 

-

 

Max_Pres_Value

 

REAL

 

-

 

O

 

-

 

Resolution

 

REAL

 

-

 

O

 

-

 

COV_Increment

 

REAL

 

0

 

O

 

W

 

Time_Delay

 

Unsigned

 

-

 

O

 

-

 

Notification_Class

 

Unsigned

 

-

 

O

 

-

 

High_Limit

 

REAL

 

-

 

O

 

-

 

Low_Limit

 

REAL

 

-

 

O

 

-

 

Deadband

 

REAL

 

-

 

O

 

-

 

Limit_Enable

 

BACnetLimitEnable

 

-

 

O

 

-

 

Event_Enable

 

BACnetEventTransitionBits

 

-

 

O

 

-

 

Acked_Transitions

 

BACnetEventTransitionBits

 

-

 

 

O

 

-

 

Notify_Type

 

BACnetNotifyType

 

-

 

O

 

-

 

Event_Time_Stamps

 

BACnetArray[N] of

 

BACnetTimeStamp

 

-

 

O

 

-

 

Profile_Name

 

CharacterString

 

-

 

O

 

-

 

 
 

 

Содержание MH-RC-BAC-1

Страница 1: ...sbishi Heavy Industries Air Conditioning Compatible with RAC Series FD Series KX6 and KXR6 VRF Series air conditioners commercialized by Mitsubishi Heavy Industries RAC Series require optional SC BIKN...

Страница 2: ...under a license agreement or nondisclosure agreement The software may be used only in accordance with the terms of those agreements No part of this publication may be reproduced stored in a retrieval...

Страница 3: ...d IntesisBox is a registered trademark of Intesis Software SLU Gateway for the integration of Mitsubishi Heavy Industries air conditioning units in BACnet enabled monitoring and control systems Compat...

Страница 4: ...ent Management BIBBs 10 Scheduling BIBBs 11 Trending BIBBs 11 Network Management BIBBs 11 Device Management BIBBs 12 4 Service Types 13 5 Objects 14 Supported Object Types 14 Member objects 15 5 2 1 T...

Страница 5: ...tPoint Analog Value Object Type 40 5 3 24 OccupiedHeatSetPoint Analog Value Object Type 41 5 3 25 UnoccupiedCoolSetPoint Analog Value Object Type 42 5 3 26 UnoccupiedHeatSetPoint Analog Value Object T...

Страница 6: ...utomation To do it so IntesisBox allows BACnet communication allowing polling or subscription requests COV IntesisBox makes available the Mitsubishi Heavy Industries air conditioning system indoor uni...

Страница 7: ...and its associated elements Element Max Notes Number of indoor units 1 Number of indoor units that can be controlled through IntesisBox Number of Objects 32 Number of Mitsubishi Heavy Industries AC si...

Страница 8: ...ties and functionalities as BACnet Objects BACnet Standardized Device Profile Annex L BACnet Operator Workstation B OWS BACnet Building Controller B BC BACnet Advanced Application Controller B AAC BAC...

Страница 9: ...ARCNET Ethernet Ethernet MS TP etc Annex H BACnet Tunneling Router over IP BACnet IP Broadcast Management Device BBMD Does the BBMD support registrations by Foreign Devices Yes No Character Sets Suppo...

Страница 10: ...B SubscribeCOV ConfirmedCOVNotification UnconfirmedCOVNotification DS COVP A Data Sharing COVP A SubscribeCOV ConfirmedCOVNotification UnconfirmedCOVNotification DS COVP B Data Sharing COVP B Subscri...

Страница 11: ...mated Trend Retrieval B ConfirmedEventNotification ReadRange BIBB Type Active BACnet Service Initiate Execute T VMT A Trending Viewing and Modifying Trends A ReadRange T VMT I B Trending Viewing and M...

Страница 12: ...sage B ConfirmedTextMessage UnconfirmedTextMessage DM TS A Device Management TimeSynchronization A TimeSynchronization DM TS B Device Management TimeSynchronization B TimeSynchronization DM UTC A Devi...

Страница 13: ...eadFile AtomicWriteFile Object Access Services AddListElement RemoveListElement CreateObject DeleteObject ReadProperty ReadPropertyConditional ReadPropertyMultiple ReadRange WriteProperty WritePropert...

Страница 14: ...rature_command Analog Value 2 OnTimeCounter OccupiedCoolSetPoint OccupiedHeatSetPoint UnoccupiedCoolSetPoint UnoccupiedHeatSetPoint Averaging 18 Binary Input 3 OnOff_status ErrorActive FIlterSign Bina...

Страница 15: ...f_command BO 0 Mode_status MI 0 Mode_command MO 0 SetPoint_status AI 0 SetPoint_command AO 0 FanSpeed_status MI 1 FanSpeed_command MO 1 AirDirectionUD_status MI 2 AirDirectionUD_command MO 2 RoomTempe...

Страница 16: ...more information 5 3 1 Mitsubishi Heavy Industries AC Gateway Device Object Type Property Identifier Property Datatype Value ASHRAE IBOX Object_Identifier BACnetObjectIdentifier Device 246000 R R Obj...

Страница 17: ...Unsigned 0 R R Configuration_Files BACnetArray N of BACnetObjectIdentifier O Last_Restore_Time BACnetTimeStamp O Backup_Failure_Timeout Unsigned16 O Active_COV_ Subscriptions List of BACnetCOVSubscrip...

Страница 18: ...ring O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 U...

Страница 19: ...FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Polarity BACnetPolarity NORMAL 0 R R Inactive_Tex...

Страница 20: ...O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of_Servic...

Страница 21: ...Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Number_Of_Sta...

Страница 22: ...ags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of_Service BOOLEAN F...

Страница 23: ...FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Update_Interval Unsigned O Units BACnetEngineeringUnits...

Страница 24: ...O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of_Servi...

Страница 25: ..._Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Number_Of_St...

Страница 26: ...cterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Ou...

Страница 27: ...CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEA...

Страница 28: ...ANALOG_INPUT 0 R R Present_Value REAL 10 50 R R Description CharacterString O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventStat...

Страница 29: ..._Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service...

Страница 30: ...racterString O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED...

Страница 31: ...Type MULTISTATE_INPUT 13 R R Present_Value Unsigned 1 92 R R Description CharacterString O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEv...

Страница 32: ..._Value State_Text 1 32 E30 63 E61 2 CommError 33 E31 64 E62 3 E1 34 E32 65 E63 4 E2 35 E33 66 E64 5 E3 36 E34 67 E65 6 E4 37 E35 68 E66 7 E5 38 E36 69 E67 8 E6 39 E37 70 E68 9 E7 40 E38 71 E69 10 E8 4...

Страница 33: ...haracterString O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTE...

Страница 34: ...ue REAL R R Description CharacterString O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACn...

Страница 35: ...E R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Polarity BACnetPolarity NORMAL 0 R R Inactive_Text Characte...

Страница 36: ...UE 2 R R Present_Value REAL 0 65535 R R Description CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetRelia...

Страница 37: ..._Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTH...

Страница 38: ...SE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Polarity BACnetPolarity NORMAL 0 R R Inactive_Text Charact...

Страница 39: ...String O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R...

Страница 40: ...32 C 60 90 F R R Description CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECT...

Страница 41: ...32 C 60 90 F R R Description CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECT...

Страница 42: ...16 32 C 60 90 F R R Description CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DET...

Страница 43: ...16 32 C 60 90 F R R Description CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DET...

Страница 44: ...racterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN F...

Страница 45: ...W W Description CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_O...

Страница 46: ...BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Inactive_Text Chara...

Страница 47: ...nt_Value REAL R R Description CharacterString O Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliabilit...

Страница 48: ...cterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FAL...

Страница 49: ...RC as master its PCB switch must be set as Master and the MH RC BAC 1 must be configured as Slave If we want to use the RC as slave its PCB switch must be set as Slave and the MH RC BAC 1 must be con...

Страница 50: ...can be configured using SW2 DIP Switch Binary value b7 b0 Decimal value Switches 1 2 3 4 5 6 7 8 MAC address 0000000x 0 x 0 1000000x 1 x 1 0100000x 2 x 2 1100000x 3 x 3 1011111x 125 x 125 0111111x 126...

Страница 51: ...the configuration tool and select either DHCP or another static IP recommended that suits your integration project requirements Check section 7 5 for more information 6 3 1 BACnet Device Instance If t...

Страница 52: ...that gateway is working properly is to check physical connections 1 Make sure that the supplied cable is correctly connected between the AC unit and the gateway MH RC BAC 1 needs to be connected to th...

Страница 53: ...UHS Default value for setpoint temperature to be set when Occupancy Unoccupancy is enabled and current mode is heat UHS must always be smaller or equal to OHS Difference between OCS and OHS must be gr...

Страница 54: ...alue Heat On OCS Room temperature OHS UCS UHS depending on current mode If Fan or Dry mode is active no setpoint is sent Current mode On Deadband action 1 Off Deadband action 0 These checks will be do...

Страница 55: ...same network domain in order to connect The default IP is 192 168 100 246 7 5 1 Home Once you reach the page remember to login with your user and password To access the login site click on User or use...

Страница 56: ...s IP seetings and AC settings can be configured Each type of parameter is grouped in different blocks 7 5 3 Signals On this section a complete list of the available BACnet objects their type Object In...

Страница 57: ...of Intesis Software SLU When you click on Edit you will have the change of introducing a new value to be applied and also the priority NOTE If you want to relinquish the selected priority please use...

Страница 58: ...ded wires twisted or with ferrule 1 core 0 5 2 5mm2 2 cores 0 5 1 5mm2 3 cores not permitted Console Port Mini USB port for console usage Mounting Wall DIN rail EN60715 TH35 BACnet MS TP port 1 x EIA4...

Страница 59: ...by mixed setting method 14 16 E14 Communication error between master and slave indoor units 16 18 E16 Indoor fan motor anomaly 19 21 E19 Indoor unit operation check drain motor check setting error 28...

Страница 60: ...thermistor anomaly 56 58 E56 Power transistor temperature thermistor anomaly 57 59 E57 Insufficient in refrigerant amount or detection of service valve closure 58 60 E58 Anomalous compressor by loss o...

Отзывы: