IntesisBox
®
BACnet
– RAC, FD, KX6 and KXR6 (VRF) series
User Manual r1.0 eng
URL
tel
http://www.intesisbox.com
[email protected]
+34 938047134
20/60
© Intesis Software S.L.U. - All rights reserved
IntesisBox
is a registered trademark of Intesis Software SLU
5.3.4 Mode_status (Multistate Input Object Type)
It indicates the active mode for the indoor unit.
Property Identifier
Property Datatype
Value
ASHRAE IBOX
Object_Identifier
BACnetObjectIdentifier
(Multi-state Input, 0)
R
R
Object_Name
CharacterString
“Mode_status”
R
R
Object_Type
BACnetObjectType
MULTISTATE_INPUT (13)
R
R
Present_Value
Unsigned
1 ~ 5
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE/TRUE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Number_Of_States
Unsigned
5
R
R
State_Text
BACnetArray[N] of
CharacterString
Check Mode Status setting table below.
O
R
Time_Delay
Unsigned
-
O
-
Notification_Class
Unsigned
-
O
-
Alarm_Values
List of Unsigned
-
O
-
Fault_Values
List of Unsigned
-
O
-
Event_Enable
BACnetEventTransitionBits
-
O
-
Acked_Transitions
BACnetEventTransitionBits
-
O
-
Notify_Type
BACnetNotifyType
-
O
-
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
-
Profile_Name
CharacterString
-
O
-
Mode status setting table
Mode status interpretation is possible using the value in the following correspondence table.
Pesent_Value
Contents displayed in State_Text
1
Heat
2
Cool
3
Fan
4
Dry
5
Auto