5.3.31 CenterRemote (Multistate Input Object Type)
It indicates the current status of the center and remote control.
Property Identifier
Property Datatype
Value
ASHRAE IBOX
Object_Identifier
BACnetObjectIdentifier
(Multi-state Input, 9)
R
R
Object_Name
CharacterString
“CenterRemote”
R
R
Object_Type
BACnetObjectType
MULTISTATE_INPUT(13)
R
R
Present_Value
Unsigned
1 ~ 6
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Number_Of_States
Unsigned
6
R
R
State_Text
BACnetArray[N] of
CharacterString
Check Center Remote table below.
O
R
Time_Delay
Unsigned
-
O
-
Notification_Class
Unsigned
-
O
-
Alarm_Values
List of Unsigned
-
O
-
Fault_Values
List of Unsigned
-
O
-
Event_Enable
BACnetEventTransitionBits
-
O
-
Acked_Transitions
BACnetEventTransitionBits
-
O
-
Notify_Type
BACnetNotifyType
-
O
-
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
-
Profile_Name
CharacterString
-
O
-
Center Remote values table
Check possible Occupancy values in the following correspondence table.
Pesent_Value
Contents displayed in State_Text
1
Center I
2
Remote I
3
Center/Remote I
4
Center II
5
Remote II
6
Center/Remote II