Condition
Setpoint
Mode
On/Off
Room temperature > OCS
Current UCS value
Cool
On
Room temperature < OHS
Current UHS value
Heat
On
OCS < Room temperature > OHS
UCS/UHS depending on current mode
(If Fan or Dry mode is active, no setpoint is sent)
Current
mode
On
(Deadband action =1)
Off
(Deadband action =0)
These checks will be done each time the indoor unit occupancy status is changed, and if
check continuously
checkbox is checked, also each time the room temperature changes.
The configuration set on the occupany signals is applied from the very first moment the occupancy signal is enabled
until the user changes the setpoint, mode or the On/Off signal, which disables occupancy functionality.