59 / 63
34
Control_ Lock Control Objects
1 bit
DPT_Bool
1.002
W T
0 - Unlocked; 1 - Locked
Special Modes
35
Control_ Power Mode
1 bit
DPT_Start
1.010
W T 0 - Stop; 1 - Start
36
Control_ Econo Mode
1 bit
DPT_Start
1.010
W T
0 - Stop; 1 - Start
37
Control_ Additional Heat
1 bit
DPT_Start
1.010
W T
0 - Stop; 1 - Start
38
Control_ Additional Cool
1 bit
DPT_Start
1.010
W T
0 - Stop; 1 - Start
Scenes
39
Control_ Save/Exec Scene
1 byte
DPT_SceneControl
18.001 W T
0 to 4 - Exec. Scene 1 to 5;
128 to 132 - Save Scene 1 to 5
40
Control_ Store Scene1
1 bit
DPT_Bool
1.002
W 1 - Store Scene
41
Control_ Store Scene2
1 bit
DPT_Bool
1.002
W 1 - Store Scene
42
Control_ Store Scene3
1 bit
DPT_Bool
1.002
W 1 - Store Scene
43
Control_ Store Scene4
1 bit
DPT_Bool
1.002
W 1 - Store Scene
44
Control_ Store Scene5
1 bit
DPT_Bool
1.002
W 1 - Store Scene
45
Control_ Execute Scene1
1 bit
DPT_Bool
1.002
W T 1 - Execute Scene
46
Control_ Execute Scene2
1 bit
DPT_Bool
1.002
W T 1 - Execute Scene
47
Control_ Execute Scene3
1 bit
DPT_Bool
1.002
W T
1 - Execute Scene
48
Control_ Execute Scene4
1 bit
DPT_Bool
1.002
W T 1 - Execute Scene
49
Control_ Execute Scene5
1 bit
DPT_Bool
1.002
W T 1 - Execute Scene
Disabling
50
Control_ Disable Input 1
1 bit
DPT_Bool
1.002
W T
0 - Enable; 1 - Disable
Control_ Disable Input 1
1 bit
DPT_Enable
1.003
W T 0 - Disable; 1 - Enable
51
Control_ Disable Input 2
1 bit
DPT_Bool
1.002
W T 0 - Enable; 1 - Disable