IntesisBox
®
KNX
– Mitsubishi Electric A.C.
User's manual r2.3 eng
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SLU
URL
Email
tel
http://www.intesisbox.com
[email protected]
+34 938047134
13 / 63
4.2 Mode Configuration dialog
Figure 4.6
Default Mode Configuration dialog
All the parameters in this section are related with the different mode properties and
communication objects.
The byte-type communication object for Mode works with the DTP_20.105. Auto mode will
be enabled with a
“0”
value, Heat mode with a
“1”
value, Cool mode with a
“3”
value, Fan
mode with a
“9”
value and Dry mode with a
“14”
value.
4.2.1 Indoor unit has FAN mode
This parameter has to be used to indicate if the indoor unit has the
fan mode
available.
o
If set to
“no”
,
the indoor unit doesn’t have the
fan mode
available.
o
If set to
“yes”
, the infoor unit has the
fan mode
available.
Important:
Read the documentation of your indoor unit to check if it has FAN mode
available.
4.2.2 Enable use of Heat / Cool bit-type obj
This parameter shows/hides the
Control_
and
Status_ Mode Cool/Heat
communication
objects.
o
If set to
“no”
the objects will not be shown.
o
If set to
“yes”
the
Control_
and
Status_ Mode Cool/Heat
objects will appear.