When
“
Execute Scene (internal)
”
is selected
, the binary input “x” will activate the
“
Scene 1
”
, on a rising edge (contact activated).
Figure 4.52
Parameter detail
➢
Scene 1 when contact is activated
The scene 1 will be activated on a rising edge. This scene MUST be defined in the
“
Scene Configuration
”
dialog as an internal preset.
o
When
“
Occupancy
(internal)”
is selected, t
he binary input “x” will
have the same
behavior as configured in the parameter “
Enable use of Occupancy function
” inside the
“Switch
-
Off Timeouts Configuration” dialog.
Figure 4.53
Parameter detail
o
When
“
Window Contact (int
ernal)”
is selected, the binary input “x” will
have the
same behavior as configured in the parameter “
Enable use of Open Window / Switch off
timeout function
” inside the “Switch
-
Off Timeouts Configuration” dialog.
Figure 4.54
Parameter detail