4.3 Special Modes Configuration dialog
Figure 4.9
Default Special Modes Configuration dialog
The Special Modes can be parameterized through the ETS parameters dialog, and they can
be used to give extra functionality.
Important:
When executing any of the Special Modes the real state of the indoor unit
will NOT be shown in KNX.
Important:
When the predefined time for the Special Mode is finished or a
“0”
value is
sent to stop it, the previous state will be recovered.
Important:
If a value concerning On/Off, Mode, Fan Speed or Setpoint Temperature is
received from KNX while any Special Mode is running (
“1”
), the Special Mode will stop
and the previous state will be recovered. The value received will be also applied then.
Important:
If a value concerning On/Off, Mode, Fan Speed or Setpoint Temperature is
modified through the remote controller, the Special Mode will stop WITHOUT recovering
the previous state. Then the real indoor unit state will be shown in KNX including the
new value received through the remote controller.
4.3.1 Enable use of POWER mode
This parameter shows/hides the
Control_ Power Mode
and
Status_ Power Mode
communication objects. The Power Mode lets change the Setpoint Temperature and the Fan
Speed within a given period of time.
o
If set to
“no”
the objects will not be shown.
o
If set to
“yes”
the
Control_ Power Mode
and
Status_ Power Mode
objects and new
parameters will appear.