4.1 General dialog
Inside this parameter
’s
dialog it is possible to activate or change the parameters shown in
the
Figure 4.1
.
The first field shows the URL where to download the database and the user manual for the
product.
4.1.1 Send READs for Control_ objects on bus recovery
When this parameter is enabled, ME-AC-KNX-1i will send READ telegrams for the group
addresses associated on its
Control_
objects on bus recovery or application reset/start-up.
o
If set to
“no”
the gateway will not perform any action.
o
If set to
“yes”
all
Control_
objects with both Transmit
(T)
and Update
(U)
flags enabled
will send READs and their values will be updated with the response when received.
Figure 4.3
Parameter detail
➢
Delay before sending READs (sec):
With this parameter, a delay can be configured between 0 and 30 seconds for the
READs sent by the
Control_
objects. This is to give time enough to other KNX
devices on the bus to start-up before sending the READs.
4.1.2 Scene to load on bus recovery / startup
This parameter executes a selected scene on bus recovery or startup, only if the selected
scene has an enabled preset or values previously saved from KNX bus (see Scene
Configuration dialog).
If the gateway is disconnected from the indoor unit the scene will not be applied, even when
connecting to the indoor unit again.
Figure 4.4
Parameter detail
4.1.3 Disallow control from remote controller
This parameter allows:
1-
Having the remote controller always locked, or
2-
Decide through a new communication object if the RC is locked or not.
o
If set to
“yes”
all the actions performed through the remote controller will be disabled.