When
“
When output value is On
”
is selected, everytime a
“1”
value is
sent, it will be sent cyclically. Also a new parameter will appear (see below).
•
When
“
When output value is Off
”
is selected, everytime a
“0”
value is
sent, it will be sent cyclically. Also a new parameter will appear (see below).
•
When
“Always”
is selected, the binary input will send any value cyclically.
Also a new parameter will appear (see below).
•
When
“Never”
is selected, cyclical sending will be disabled.
➢
Period for cyclical sending (seconds)
This parameter lets configure a time (in seconds) for the cyclical sending.
Figure 4.44
Parameter detail
o
When
“
Dimming
”
is selected the communication objects and new parameters for the
Input “x” will appear as shown below.
Figure 4.45
Parameter detail
➢
Send telegram after bus recovery
This parameter lets
select if the Binary Input “x” will send a telegram, or not, after a
bus recovery, and the type of telegram sent (if enabled).
•
When
“No action”
is selected, no telegram will be sent after a bus recovery.
•
When
“On”
is selected, the binary input will send a telegram with a
“1”
value
after a bus recovery. Also a new parameter will appear (see below).
•
When
“Off”
is selected, the binary input will send a telegram with a
“0”
value
after a bus recovery. Also a new parameter will appear (see below).