4.9.4 Disabling function
This parameter shows/hides the
Control_ Disable Input x
communication object which will
let disable/enable the input x.
o
If set to
“no”
any object will be shown.
o
When
“DPT 1.003: 0
-Disable; 1-Enable
”
is selected, the input can be disabled using
the value
“0”
and enabled using the value
“1”
.
o
When
“DPT 1.002: 0
-Enable; 1-
Disable”
is selected, the input can be disabled using
the value
“1”
and enabled using the value
“0”
.
4.9.5 Function
This parameter lets choose the function that will have the binary input. There are 7 different
functions available: Switching, Dimming, Shutter/Blind, Value, Execute Scene (internal),
Occupancy (internal) and Window Contact (internal).
o
When
“Switching”
is selected the communication object and new parameters for the
Input “x” will appear as shown below.
Figure 4.42
Parameter detail
➢
Send telegram after bus recovery
This parameter lets
select if the Binary Input “x” will send a telegram, or not, after a
bus recovery, and the type of telegram sent (if enabled).
•
When
“No action”
is selected, no telegram will be sent after a bus recovery.
•
When
“Current status”
is selected, the binary input will send a telegram
with its current status after a bus recovery. Also a new parameter will appear
(see below).