Appendix A
– Communication Objects Table
TOPIC
OBJECT
NUMBER
NAME
LENGTH
DATAPOINT TYPE
FLAGS
FUNCTION
DPT_NAME
DPT_ID R W T U
On/Off
0
Control_ On/Off
1 bit
DPT_Switch
1.001
W T 0 - Off; 1-On
Mode
1
Control_ Mode
1 byte DPT_HVACContrMode 20.105 W T
0 - Auto; 1 - Heat; 3 - Cool; 9 - Fan; 14 - Dry
2
Control_ Mode Cool/Heat
1 bit
DPT_Heat/Cool
1.100
W T 0 - Cool; 1 - Heat;
3
Control_ Mode Cool & On
1 byte
DPT_Scaling
5.001
W T 0% - Off; 0.1%-100% - On + Cool
4
Control_ Mode Heat & On
1 byte
DPT_Scaling
5.001
W T
0% - Off; 0.1%-100% - On + Heat
5
Control_ Mode Auto
1 bit
DPT_Bool
1.002
W T 1 - Auto
6
Control_ Mode Heat
1 bit
DPT_Bool
1.002
W T 1 - Heat
7
Control_ Mode Cool
1 bit
DPT_Bool
1.002
W T
1 - Cool
8
Control_ Mode Fan
1 bit
DPT_Bool
1.002
W T 1 - Fan
9
Control_ Mode Dry
1 bit
DPT_Bool
1.002
W T 1 - Dry
10
Control_ Mode +/-
1 bit
DPT_Step
1.007
W 0 - Decrease; 1 - Increase
Control_ Mode +/-
1 bit
DPT_UpDown
1.008
W 0 - Up; 1 - Down
Fan Speed
11
Control_ Fan Speed / 2 Speeds
1 byte
DPT_Scaling
5.001
W T 0%-74% - Speed 1; 75%-100% - Speed 2;
Control_ Fan Speed / 2 Speeds
1 byte
DPT_Enumerated
5.010
W T
1 - Speed 1; 2 - Speed 2;