4.4
Global temperature configuration
Figure 4.20
Default Temperature Configuration dialog
All the parameters in this section are related with the Temperature properties and
communication objects.
4.4.1
Enable use of +/- obj for Setpoint
This parameter shows/hides the
Control_ Setpoint Temp +/-
communication object which lets
you change the indoor unit setpoint temperature by using two different datapoint types.
18:
o
If set to
“no”
the object will not be shown.
o
If set to
“yes”
the
Control_ Setpoint Temp +/-
object and a new parameter will appear.
Figure 4.23
Parameter detail
➢
DPT type for +/- Setp Temp object
This parameter lets choose between the datapoints
0-Up / 1-Down [DPT_1.008]
and
0-Decrease / 1-Increase [DPT_1.007]
for the
Control_ Setpoint Temp +/-
object.
4.4.2
Ambient Ref. Temp. is provided from KNX
▪
Up / Increase
▪
Down / Decrease
…
16ºC
17ºC
32ºC
31ºC
(Upper limit)
(Lower limit)