Appendix A – Communication Objects Table
SECTION
OBJECT
NUMBER
NAME
LENGTH
DATAPOINT TYPE
FLAGS
FUNCTION
DPT_NAME
DPT_ID R W T U
On/Off
1
Control_ On/Off
1 bit
DPT_Switch
1.001
W T 0 - Off; 1-On
Mode
2
Control_ Operating Mode
1 byte
DPT_HVACMode
20.102
W T 0 - Auto; 1 - Com; 2 - Stan; 3 - Eco; 4
–
Pro
3
Control_ Mode
1 byte
DPT_HVACControl
20.105
W T 0 - Auto; 1 - Heat; 3 - Cool; 9 - Fan; 14 - Dry
4
Control_ Mode Cool/Heat
1 bit
DPT_Cool/Heat
1.100
W T 0 - Cool; 1
–
Heat
5
Control_ Mode Auto
1 byte
DPT_Scaling
5.001
W T 1 - Auto
6
Control_ Mode Heat
1 byte
DPT_Scaling
5.001
W T 1 - Heat
7
Control_ Mode Cool
1 bit
DPT_Bool
1.002
W T 1 - Cool
8
Control_ Mode Fan
1 bit
DPT_Bool
1.002
W T 1
–
Dry
9
Control_ Mode Dry
1 bit
DPT_Bool
1.002
W T 1
–
Fan
10
Control_ Mode +/-
1 bit
DPT_Step
1.007
W 0 - Decrease; 1 - Increase
Control_ Mode +/-
1 bit
DPT_UpDown
1.008
W 0 - Up; 1 - Down
Fan Speed
11
Control_ Fan Speed / 3 Speeds
1 byte
DPT_Scaling
5.001
W T
0%-49% - Speed 1; 50%-83% - Speed 2;
84%-100% Speed 3
Control_ Fan Speed / 3 Speeds
1 byte
DPT_Enumerated
5.010
W T 1 - Speed 1; 2 - Speed 2; 3 Speed 3
12
Control_ Fan Speed Man/Auto
1 bit
DPT_Bool
1.002
W T 0
–
Manual; 1
–
Auto
13
Control_ Fan Speed 1
1 bit
DPT_Bool
1.002
W T 1 - Fan Speed 1
14
Control_ Fan Speed 2
1 bit
DPT_Bool
1.002
W T 1 - Fan Speed 2
15
Control_ Fan Speed 3
1 bit
DPT_Bool
1.002
W T 1 - Fan Speed 3
16
Control_ Fan Speed +/-
1 bit
DPT_Step
1.007
W T 0 - Decrease; 1 - Increase
Control_ Fan Speed +/-
1 bit
DPT_UpDown
1.008
W T 0 - Up; 1 - Down