Intesis
Box
®
KNX - Haier A.C. (VRF line)
User's manual r1.0 EN
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox is a registred trademark of
Intesis Software SLU
URL
tel
http://www.intesisbox.com
[email protected]
+34 938047134
12 / 31
o
If set to
“
Enabled
”
the
Control_
and
Status_ Mode Cool/Heat
objects will appear.
•
When a
“1”
value is sent to the
Control_
communication object,
Heat mode
will be enabled in the indoor unit, and the
Status_
object will return this value.
•
When a
“0”
value is sent to the
Control_
communication object,
Cool mode
will be enabled in the indoor unit, and the
Status_
object will return this value.
4.2.3
Enable use of + / - object for Mode
This parameter shows/hides the
Control_ Mode +/-
communication object which let
’
s you
change the indoor unit mode by using two different datapoint types.
10:
o
If set to
“
Disabled
”
the object will not be shown.
o
If set to
“
Enabled
”
the
Control_ Mode +/-
object and a new parameter will appear.
Figure 4.11
Parameter detail
➢
DPT type for +/- Mode Object
This parameter lets choose between the datapoints
0-Up / 1-Down [DPT_1.008]
and
0-Decrease / 1-Increase [DPT_1.007]
for the
Control_ Mode +/-
object.
The sequence followed when using this object is shown below:
Keep in mind that depending on the indoor unit you have and the available features,
Auto mode and Dry mode may not be present.
4.2.4
Enable use of bit-type Mode objects (for control)
This parameter shows/hides the bit-type
Control_ Mode
objects.
5:
6:
7:
8:
▪
Up / Increase
▪
Down / Decrease
DRY
AUTO
HEAT
COOL
FAN