4 P/N 466-5307
• REV A • ISS 15MAR17 ©2017 United Technologies Corporation
1. After selecting the proper location for the detector, attach the mounting bracket
(trim plate) to the wall or ceiling. To ensure aesthetic alignment of the detector with
the hallway, or wall, the "A" line on the mounting bracket (trim plate) must be
parallel with the hallway when ceiling mounted, or horizontal when wall mounted.
2. Install the detector fully on the mounting bracket (trim plate) by rotating the
detector in a clockwise direction.
NOTE:
Installing the detector on the mounting bracket (trim plate) will automatically
activate the battery. The power up sequence is indicated by the LED ring slowly
blinking GREEN one time.
NOTE:
Detectors will emit a series of slow RED LED blinks as the unit searches
for a wireless network. If you are intending to use the detectors without the
wireless interconnect function, ignore these notifications, and the wireless
interconnect function will eventually turn off (~15 minutes OR to immediately close
the network, push the Test/Hush button until two beeps are heard (approximately 4
seconds) and then release the button.
•
Network closed sound on each detector confirms network has been
closed. GREEN LED flashes once every 60 seconds to indicate normal
operation.
NOTE:
The battery activation is a one-time feature. After activation, the battery
cannot be turned off, and can only be discharged at the end of unit life. If the
detector is removed from the mounting plate, the battery will remain active. See
Permanently Disable Detector / Discharge Battery section to de-energize the
detector.
WIRELESS INTERCONNECT
A maximum of 24 compatible devices may be interconnected in a multiple station
arrangement. The interconnect system should not exceed the NFPA interconnect limit
of 12 smoke detectors and/or 18 detectors total (smoke, CO, smoke/CO combination,
heat, etc.).
WIRELESS INTERCONNECT MODEL COMPATIBILITY
The following Interlogix model can be interconnected using wireless interconnect:
•
SDX-135Z
•
Maximum distance between wireless interconnect models is 300 feet in open air.
Set up a Wireless Detector Network (Wireless Interconnect)
Creating a wireless
interconnect network is a simple process, with intelligent “self-
enrollment” features.
1. Remove all wireless detectors from their packaging (suggest using a table and
activating all detectors in a group).