![Interlogix CDX-135Z Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/interlogix/cdx-135z/cdx-135z_installation-manual_2077323010.webp)
10 P/N 466-5307
• REV A • ISS 15MAR17 ©2017 United Technologies
Corporation
returned for service. See Permanently Disable Detector/Discharge Battery section to
determine how to prepare the unit for shipment or disposal.
WARNING: DO NOT USE AN OPEN FLAME TO TEST YOUR DETECTOR.
YOU COULD DAMAGE THE DETECTOR OR IGNITE COMBUSTIBLE MATERIALS
AND START A STRUCTURE FIRE.
FUNCTIONAL SMOKE TEST
The smoke test verifies that the unit activates when detecting smoke, that the
transmitted signal is received by the receiver/panel, and that the panel reports the
alarm to the central monitoring station. The smoke test should be performed annually.
A canned smoke testing agent must be used for the functional smoke test
NOTE:
Use Interlogix brand of Smoke! In A Can part number SM-200.
1. Wait at least 90 seconds after installation to test the smoke detector.
2. Make sure the GREEN LED is flashing for normal operation (one GREEN LED
blink every 60 seconds).
3. From a distance of 2 - 4 feet (0.6
– 1.2m), aim spray for 1 – 2 seconds at the vents
or side of the detector.
4. The alarm will sound within 1
– 10 seconds if the detector functions properly.
5. Press the Test/Hush button to quiet the sounder.
6. Contact the central monitoring station to verify they received the alarm report.
7. Alert the central monitoring station when you are finished testing.
NOTE:
An alternative method for performing a functional smoke test in the field is to
hold a smoldering punk or cotton wick close to the detector and direct the smoke into
the vent openings until an alarm is indicated.
CO INSPECTION AND FUNCTIONAL GAS TEST
A canned CO testing agent must be used for the CO functional gas test. Contact a local
supplier for canned CO gas
– Solo C6
TM
CO Detector Tester.
NOTE:
Cans of Solo C6
TM
CO Detector Tester can be sourced from the manufacturer
per the following contact information:
Product Code: Solo C6-024
SDi, 1345 Campus Parkway, Suite A18, Wall Township, NJ 07753 USA
Tel: (732) 751-9266, Fax: (732) 751-9241
Email: [email protected], Web: www.sdifire.com
1. Wait at least 20 minutes after installation to test the CO detector.