13 P/N 466-5307
• REV A • ISS 15MAR17 ©2017 United Technologies
Corporation
Operational Mode
Visual Indication
Audible
Indication
Action:
Smoke/Heat (Fire)
Alarm
On all alarming
detectors, the
RED LED blinks
per a Temporal
T3 Pattern
Temporal T3
alarm pattern is
three long blinks,
1.5 second pause,
three long blinks,
repeating.
On the detector
initiating the
Smoke/Heat
Alarm only, the
GREEN LED will
blink every
second.
Alarm per
Temporal T3
Pattern
Temporal T3
alarm pattern is
three long beeps,
1.5 second pause,
three long beeps,
repeating.
Smoke/fire has been detected.
Follow the instructions at the
beginning of this User Guide
under the section "What to do
when the alarm sounds,
Smoke/Heat alarm activation"
Freeze Warning
One RED LED
blink every 20
seconds.
None
None. Flashing continues
while condition exists.
Tamper Condition
One RED LED
blink every 30
seconds.
Detector chirps
once when
tamper condition
is first sensed,
then the detector
will chirp every 30
seconds after a 3
minute delay.
Reattach detector to its trim
plate, otherwise flashing and
chirping will continue while
condition exists.
Fault Mode/Fatal
Error
One AMBER LED
blink every 5
seconds.
Detector chirps
every 30 seconds.
Flashing/chirping continues
while condition exists.
Remove detector from service.
If fatal error cannot be cleared,
permanently discharge and
decommission the detector.
System Test Mode
Rapidly flashing
RED LED for 10
seconds duration
1 detector chirp
when magnet
detected, 2
detector chirps
when System
Test mode
enabled
Hold magnet next to button for
4 seconds as described in
User Guide.
Local Detector Test
(button press when
no alarm condition
is present)
Flashes RED,
AMBER, GREEN,
then current
protocol
Temporal T3 and
T4 patterns
Allow completion of test or
perform button press to cancel
before end of countdown -
return to normal operation