NSN 6130-99-391-3441 ()
Battery Charger Analyser : Operator Manual
6
Battery Charge Operation
6.1
Lead Acid Constant Voltage Charge
6.1.1
Parameters Required
a) Target constant voltage.
This is the constant voltage target value that the charger will maintain during
the charge cycle.
b) Maximum charge current.
This value of current is the maximum current that he charger will charge the
battery at before it achieves it's constant voltage mode.
c) Duration of complete charge.
This time is the maximum time that the charger is to charge the battery before
termination.
d) Minimum charge current.
Sets the value of current that when reached terminates the charge process.
This value is optional and should be set to zero if not required.
e) Current threshold.
This sets a safety point that once the charger has reached it's maximum
current: the current would normally fall. If the charge current then proceeds to
rise to a value greater than this setting then the charge process is terminates,
indicating that there is a potential problem with the battery.
This value is optional and should be set to zero if not required.
f)
Current to potential changeover time.
If the target voltage has not been reached within this time then the charge
process is terminated indicating a battery fault.
This value is optional and should be set to zero if not required.
Doc: DWG1030-25-R11 Operators manual.odt
Page 13 of 72
Copyright Material of Intelligent Charging Limited © 2015
Printed On : 12/06/17