Intech Instruments IN-P Series Скачать руководство пользователя страница 9

 

9

 

 

 

 

 

 

 

 

6.7 

 

Edit calibration PIN: 

 

_ _ _ EDIT CAL PIN NUMBER 

scrolls across the display and toggles with 

SKIP

Press  

P  

to skip and return to the operational display, or the  

  button and then  

P  

to 

ENTER

.

 

_ _ _ ENTER NEW CAL PIN NUMBER 

scrolls across the display and toggles with the current PIN (default 

= 1). Using the  

  and  

  buttons, enter your new calibration PIN number. Then press  

P  

to exit and return to 

the  

RANGER A - 

This allows the indicator to drive a remote display from the Rinstrum range. The following shows 

the  

output string format when Ranger A output is selected: 

<Start> <Sign> <Output Value> <Status> <End>

 

 

STRING CHARACTER(S):

 

<Start>

 

STX character (ASCII 02). 

<Sign>

 

Output value sign (space for + and dash for  ). 

<Output Value>

 

Seven character ASCII string containing the current output value and decimal point.  

(If there is no decimal point, then the first character is a space. Leading zero blanking applies.) 

<Status>

 

Single character output value status: U=Under, 0=Over, E=Error. 

<End>

 

ETX character (ASCII 03). 

MODBUS REGISTERS - 

These are all holding registers and should be accessed via function codes 3 and 6. 

Register addresses are displayed in the Modicon™ addressing format. i.e. Register 65=40065 (subtract 1 for direct 

addressing). 

 

 

16-BIT

 

40001

  Alarm status (Bit 0=SP1, Bit1 

  

=SP2, Bit 2=SP3, Bit 3=SP4) 

40065

  SP 1 hysteresis 

40071

  SP 1 make delay 

40066

  SP 2 hysteresis 

40072

  SP 2 make delay 

40067 

SP 3 hysteresis 

40073

  SP 3 make delay 

40068

 

SP 4 hysteresis 

40074

 

SP 4 make delay 

40069 

SP 5 hysteresis 

40075 

SP 5 make delay 

40070 

SP 6 hysteresis 

40076 

SP 6 make delay 

32-BIT SIGNED 

(2x16-bit)  

40513

 

Process display 

40525

 

Peak 

40527 

Valley 

40535

  Setpoint 1 

40537

  Setpoint 2 

40539

  Setpoint 3 

40541

 

Setpoint 4

 

40543

 

Setpoint 5

 

40545

 

Setpoint 6

 

40587

 

D A scale low value

 

40591

 

D A scale high value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

_ _ _ CAL LOW ANALOG OUTPUT 

scrolls across the display and toggles with a calibration number.  

Using the  

  and  

  buttons, calibrate your low analogue output as required. Then press  

 

The display value is shown in internal units (mA). 

_ _ _ CAL HIGH ANALOG OUTPUT 

scrolls across the display and toggles with a calibration number.  

Using the  

  and  

  buttons, calibrate your high analogue output as required. Then press  

        The display value is shown in internal units (mA).

 

 

6.6 

 

Serial setup: 

If your indicator does not have this option installed, then you will not view this section - setup will continue at 6.7. 

 

_ _ _ SERIAL SETUP 

scrolls across the display and toggles with 

SKIP

Press  

P  

to skip to 6.7, or the  

  button and then  

P  

to 

ENTER 

serial port setup. 

_ _ _ SERIAL MODE 

scrolls across the display and toggles with the currently selected serial mode.  

Using the  

  and  

  buttons, select: 

ASCII

MODBUS 

(RTU) or 

RNGR A 

(Ranger A). Then press  

ASCII is a simple protocol that allows connection to various PC configuration tools. MODBUS is an industry  

standard RTU slave mode that allows connection to a wide range of devices, such as PC

s or PLC

s.  

RNGR A is a continuous output, used to drive remote displays and other instruments in the Rinstrum

™ 

range. (Ranger is a trade name belonging to Rinstrum Pty Ltd.) 

 

_ _ _ BAUD RATE 

scrolls across the display and toggles with the current selection.  

Use the  

  and  

  buttons to select: 

300

600

1200

2400

4800

9600

19200 

or 

38400

. Then press  

D  

_ _ _ PARITY 

scrolls across the display and toggles with the current selection.  

Use the  

  and  

  buttons to select: 

NONE

ODD 

or 

EVEN

. Then press  

E  

_ _ _ SERIAL ADDRESS 

scrolls across the display and toggles with the current selection.  

Use the  

  and  

  buttons to set the serial address, and then press  

The serial address parameter is used to identify a particular device when it is used with other devices in a system. 

(It applies particularly to Modbus mode when used on a RS485 network.) The serial address of the indicator must 

be set to match the serial address defined in the master device.

 

Содержание IN-P Series

Страница 1: ...IN P Multifunction Process Indicator Installation Guide...

Страница 2: ...tted Page 6 5 5 Wire your serial port if fitted Page 6 5 6 Wire your function pins if required Page 7 5 7 Power up your indicator Page 7 SECTION 6 Setup Calibration Page 7 6 1 Enter calibration PIN Pa...

Страница 3: ...R6 6x 5A relay outputs For PRC1 model only ANALOGUE OUTPUT RETRANSMISSION N None A 1 x 4 20mA 0 10V Analogue Output COMMUNICATIONS Not all Communication options are available for each input model type...

Страница 4: ...y will show the current VALLEY value see Section 11 E Function 2 This button is used to access the setpoint setup menu see Section 7 and the setpoint direct access menu see Section 8 SECTION 2 Specifi...

Страница 5: ...egin Before you can begin wiring the IP07 input module must be removed from the meter case so that the jumpers can be positioned for your input type Remove the plastic backing plate from the rear of t...

Страница 6: ...you do not have any relays fitted step 5 3 is skipped 5 4 Wire your analogue output if fitted Refer to 3 2I If your indicator has an analogue output fitted wire it as shown If you do not have an analo...

Страница 7: ...e the input mode in this section then the jumper plug on the input module must also be changed to match See Section 4 for more information D _ _ _ DECIMAL POINT POSITION scrolls across the display and...

Страница 8: ...lay value for cal high as at 6 5F D _ _ _ CALIBRATE ANALOG OUTPUT scrolls across the display and toggles with SKIP If you do not wish to calibrate your analogue output press P now If you would like to...

Страница 9: ...across the display and toggles with a calibration number Using the and buttons calibrate your low analogue output as required Then press P The display value is shown in internal units mA F _ _ _ CAL H...

Страница 10: ...scrolls across the display and toggles with the current selection Use the and buttons to adjust this value if required Then press P The hysteresis value defines the separation band between setpoint a...

Страница 11: ...rn to the operational display To view the minimum valley value Press the button for a second The word VALLEY appears on the display and toggles with the minimum measured process input value Press P to...

Страница 12: ...12 www intech co nz Christchurch Ph 64 3 343 0646 Auckland Ph 09 827 1930 Email sales intech co nz IN P 071216...

Отзывы: