Position your input jumpers: 

 

The IP07 input module has one jumper, which may need to be repositioned to suit your application. When you have  

finished, slide the input module back into the case and replace the plastic backing plate. 

 

 

 

JUMPER POSITIONING: 

 

 

 

 

 

 

 

 

Example showing a Jumper In & Jumper Out:

 

 

 

 

 

Before you begin:

 

Once the backing plate has been removed, gently slide the input 

module from the case (see Section 3.2J to identify the input module). 

SECTION 4. –

 

Input Jumper Configuration. 

Before you Begin: 

Before you can begin wiring, the IP07 input module must be removed from the meter case so that the jumpers can be 

positioned for your input type. Remove the plastic backing plate from the rear of the meter by inserting a screwdriver into 

the indents circled on the image below: 

20mA     

Current input (0~20mA or 

4~20mA).

 

Custom 

Custom input – call for options.

 

2V          

Voltage input (0~2V).

 

Jumper In 

Jumper Out (i.e. Jumper not fitted). 

CONNECTOR PINS: 

G - Relays 

Wiring: Section 5.3 

H - Serial port 

Wiring: Section 5.5 

I - Analogue output 

Wiring: Section 5.4 

J - IP07 input module 

Jumper setup:  Section 4 

 

Wiring: Section 5.2 

K - Function pins 

Wiring: Section 5.6 

L - Power supply (HV LV)  

Wiring: Section 5.1 

3.2 

 

Fig 2 - Rear view: 

Содержание IN-P Series

Страница 1: ...IN P Multifunction Process Indicator Installation Guide...

Страница 2: ...tted Page 6 5 5 Wire your serial port if fitted Page 6 5 6 Wire your function pins if required Page 7 5 7 Power up your indicator Page 7 SECTION 6 Setup Calibration Page 7 6 1 Enter calibration PIN Pa...

Страница 3: ...R6 6x 5A relay outputs For PRC1 model only ANALOGUE OUTPUT RETRANSMISSION N None A 1 x 4 20mA 0 10V Analogue Output COMMUNICATIONS Not all Communication options are available for each input model type...

Страница 4: ...y will show the current VALLEY value see Section 11 E Function 2 This button is used to access the setpoint setup menu see Section 7 and the setpoint direct access menu see Section 8 SECTION 2 Specifi...

Страница 5: ...egin Before you can begin wiring the IP07 input module must be removed from the meter case so that the jumpers can be positioned for your input type Remove the plastic backing plate from the rear of t...

Страница 6: ...you do not have any relays fitted step 5 3 is skipped 5 4 Wire your analogue output if fitted Refer to 3 2I If your indicator has an analogue output fitted wire it as shown If you do not have an analo...

Страница 7: ...e the input mode in this section then the jumper plug on the input module must also be changed to match See Section 4 for more information D _ _ _ DECIMAL POINT POSITION scrolls across the display and...

Страница 8: ...lay value for cal high as at 6 5F D _ _ _ CALIBRATE ANALOG OUTPUT scrolls across the display and toggles with SKIP If you do not wish to calibrate your analogue output press P now If you would like to...

Страница 9: ...across the display and toggles with a calibration number Using the and buttons calibrate your low analogue output as required Then press P The display value is shown in internal units mA F _ _ _ CAL H...

Страница 10: ...scrolls across the display and toggles with the current selection Use the and buttons to adjust this value if required Then press P The hysteresis value defines the separation band between setpoint a...

Страница 11: ...rn to the operational display To view the minimum valley value Press the button for a second The word VALLEY appears on the display and toggles with the minimum measured process input value Press P to...

Страница 12: ...12 www intech co nz Christchurch Ph 64 3 343 0646 Auckland Ph 09 827 1930 Email sales intech co nz IN P 071216...

Отзывы: