SECTION 3. –
Case Schematics.
The IN-P has a 6-digit, 14-segment alphanumeric LED display, 5 front-panel buttons and 6 setpoint annunciator LED’s.
3.1
–
Fig 1 - Front view:
BUTTON PRESS FUNCTIONS:
A - Function 1
This button is used to access the
input setup and calibration
menu. See Section 6.
B - Program
This button is typically used to save your settings and advance to the next step in the
setup process.
C - Up
This button is typically used to scroll through options or increase values in the setup menu.
Pressing this button from the main display will show the current
PEAK
value (see Section 11).
D - Down
This button is typically used to scroll through options or decrease values in the setup menu.
Pressing this button from the main display will show the current
VALLEY
value (see Section 11).
E - Function 2
This button is used to access the
setpoint setup
menu (see Section 7) and the
setpoint direct
access
menu (see Section 8).
SECTION 2. –
Specifications.
Power supply
HV: 85~265Vac / 95~370Vdc or LV: 15~48Vac / 10~72Vdc.
Sampling rate
10Hz.
Resolution
16-bit.
Accuracy
0.05% of reading.
Temperature drift
Typically 50ppm/°C.
Calibration
Factory pre-calibrated - automatic or manual user calibration available.
Security
Setup is PIN code protected.
Case
48 x 96 x 119.5mm (H x W x D) / 45.5 x 92.5mm panel cutout.
OPTIONAL
Relay outputs
2, 4 or 6 x 5A Form A relays.
Analogue output
Isolated 16-bit 4~20mA/0~10V output (fully scaleable). Window programmable over any
range within the full-scale range of the indicator.
Serial port
Isolated RS485/RS232. Modes: ASCII, Modbus RTU slave, Ranger A.
Data rates: 1200~115k2 baud. Parity: Odd, even or none.
JUMPER SELECTABLE OPTIONS
Input range jumper
20mA, Custom, 2V, 10V.