10
SECTION 7. –
Setpoint Setup.
Enter the setpoint setup mode by pressing and holding the
F2
button for 3
seconds.
7.1
–
Enter setpoint PIN:
A
_ _ _ ENTER SP PIN NUMBER
scrolls across the display and toggles with
0
. Use the
and
buttons to
enter your security code (factory default = 1). Then press
P
. If the correct PIN is entered then the setup is started
at 7.2.
If an incorrect PIN number is entered,
_ _ _ INCORRECT PIN NUMBER - ACCESS DENIED
scrolls across the
display and it returns to the normal operating mode.
You will be given the opportunity to change your PIN number at the end of this section (7.3).
If you have forgotten your PIN number, see Section 9.
7.2
–
Edit setpoints:
A
_ _ _ EDIT SETPOINT
scrolls across the display and toggles with
SKIP
. Press
P
to skip to 7.4, or use the
and
buttons to select a setpoint to edit:
SP 1
,
SP 2
,
SP 3
,
SP 4
,
SP 5
or
SP 6
. Then press
P
.
SP 3-6 are not available for models with only 2 relays installed. SP 5-6 are not available for models with only 4 relays installed.
B
_ _ _ SP VALUE
scrolls across the display and toggles with the last setpoint value entered.
Using the
and
buttons, adjust the display value at which the setpoint will activate. Then press
P
.
C
_ _ _ SP ACTIVATION
scrolls across the display and toggles with the last selected setpoint activation.
Use the
and
buttons to select
ABOVE
or
BELOW
and then press
P
.
ABOVE - relay turns on above the setpoint value and off below it.
BELOW - relay turns on below the setpoint value and off above it.
D
_ _ _ SP TYPE
scrolls across the display and toggles with the last selected setpoint type.
Using the
and
buttons, select either
ALARM
or
CNTRL
(Control). Then press
P
.
E
_ _ _ HYSTERESIS VALUE
scrolls across the display and toggles with the current selection.
Use the
and
buttons to adjust this value if required. Then press
P
.
The hysteresis value defines the separation band between setpoint activation and deactivation.
Hysteresis will operate as per the specified type setting (see 7.2D).
F
_ _ _ MAKE DELAY
scrolls across the display and toggles with the current selection.
Use the
and
buttons to adjust this value if required. Then press
P
.
This value is displayed in seconds with a 0.1 second resolution, and is the time delay before the relay energises.
G
_ _ _ OPEN ACCESS TO SP VALUE
scrolls across the display and toggles with the last selected direct ac-
cess setting. Use the
and
buttons to select either
YES
or
NO
, and then press
P
.
When enabled, this option allows the setpoint value to be edited directly after pressing the F2 button, without
needing to enter a PIN number or go through all of the other options. Each setpoint can individually have this option
enabled or disabled.
H
_ _ _ TRAIL SP1
scrolls across the display and toggles with the current trailing setting.
Using the
and
buttons, select either
OFF
or
ON
, and then press
P
.
If you choose ON, the selected setpoint will become an offset value, which is effectively added to the value of SP 1.
I
_ _ _ EDIT SETPOINT
scrolls across the display and toggles with
SKIP
. You are now back at 7.2A.
To edit another setpoint, follow the instructions from 7.2A-I. If you do not wish to edit another setpoint, press
P
now to proceed to 7.3.
ALARM
The
setpoint value
determines setpoint activation, and
the
hysteresis value
determines setpoint deactivation.
CNTRL (Control)
The
setpoint value
determines setpoint deactivation, and
the
hysteresis value
determines setpoint reactivation.
If you selected SP 1 in 7.2A:
Skip 7.2H and continue to 7.2I now.
Note:
To SKIP or ENTER values - Push
To SELECT a menu input - Push
P