MD380 User Manual Desc
ription of Function Codes
- 163 -
Value
Function
Description
10
581GLVDEOHG
The AC drive decelerates to stop, but the running
parameters are all memorized, such as PLC, wobble
function and PID parameters. After this function is
disabled, the AC drive resumes its status before stop.
11
([WHUQDOIDXOW12LQSXW
,IWKLVWHUPLQDOEHFRPHV21WKH$&GULYHUHSRUWV(UU
and performs the fault protection action. For more
details, see the description of F9-47.
12
Multi-reference terminal 1
The setting of 16 speeds or 16 other references can be
implemented through combinations of 16 states of these
four terminals.
13
Multi-reference terminal 2
14
Multi-reference terminal 3
15
Multi-reference terminal 4
16
Terminal 1 for acceleration/
deceleration time selection
Totally four groups of acceleration/deceleration time can
be selected through combinations of four states of these
two terminals.
17
Terminal 2 for acceleration/
deceleration time selection
18
Frequency source
switchover
The terminal is used to perform switchover between two
frequency sources according to the setting in F0-07.
19
83DQG'2:1VHWWLQJ
clear (terminal, operation
panel)
If the frequency source is digital setting, the terminal
LVXVHGWRFOHDUWKHPRGL¿FDWLRQE\XVLQJWKH83
'2:1IXQFWLRQRUWKHLQFUHPHQWGHFUHPHQWNH\RQWKH
operation panel, restoring the frequency reference to the
value of F0-08.
20
Command source
switchover terminal
If the command source is set to terminal control (F0-02
WKLVWHUPLQDOLVXVHGWRSHUIRUPVZLWFKRYHUEHWZHHQ
terminal control and operation panel control.
If the command source is set to communication control
) WKLVWHUPLQDOLVXVHGWRSHUIRUPVZLWFKRYHU
between communication control and operation panel
control.
21
Acceleration/Deceleration
prohibited
It enables the AC drive to maintain the current frequency
output without being affected by external signals (except
WKH6723FRPPDQG
22
PID disabled
PID is invalid temporarily. The AC drive maintains
the current frequency output without supporting PID
adjustment of frequency source.
23
PLC state reset
:KHQ3/&FRQWUROLVVWDUWHGDJDLQDIWHULWZDVGLVDEOHG
the terminal is used to restore the original status of PLC
control for the AC drive
24
:REEOHGLVDEOHG
The AC drive outputs the central frequency, and the
wobble function is disabled.
25
Counter input
This terminal is used to count pulses.
26
Counter reset
This terminal is used to clear the counter.
27
Length count input
This terminal is used to count the length.
28
Length reset
This terminal is used to clear the length.
efesotomasyon.com
Содержание MD380 Series
Страница 8: ...efesotomasyon com...
Страница 9: ...1 Safety Information and Precautions efesotomasyon com...
Страница 16: ...Safety Information and Precautions MD380 User Manual 16 efesotomasyon com...
Страница 17: ...2 Product Information efesotomasyon com...
Страница 28: ...Product Information MD380 User Manual 28 efesotomasyon com...
Страница 29: ...3 Mechanical and Electrical Installation efesotomasyon com...
Страница 46: ...Mechanical and Electrical Installation MD380 User Manual 46 efesotomasyon com...
Страница 47: ...4 Operation Display and Application Examples efesotomasyon com...
Страница 82: ...Operation Display and Application Examples MD380 User Manual 82 efesotomasyon com...
Страница 83: ...5 Function Code Table efesotomasyon com...
Страница 138: ...Function Code Table MD380 User Manual 138 efesotomasyon com...
Страница 139: ...6 Description of Function Codes efesotomasyon com...
Страница 249: ...7 EMC efesotomasyon com...
Страница 261: ...8 Selection and Dimensions efesotomasyon com...
Страница 293: ...9 Maintenance and Troubleshooting efesotomasyon com...