MD380 User Manual Product Information
- 25 -
2.4.1 Description of Peripheral Electrical Devices
Table 2-3 Description of peripheral electrical devices
Part
Mounting Location
Function Description
MCCB
Power receiving side
Interrupt the power supply when overcurrent occurs on
downstream devices
Contactor
Between MCCB and
AC drive input side
Start and stop the AC drive.
Do not start and stop the AC drive frequently by switching
the contactor on and off (less than twice per minute) nor
use it to directly start the AC drive.
AC input
reactor
AC drive input side
Improve the power factor of the input side.
Eliminate the higher harmonics of the input side
effectively and prevent other devices from being
damaged due to distortion of the voltage waveform.
Eliminate the input current unbalance due to unbalance
between the power phases.
EMC
,QSXW¿OWHU
AC drive input side
Reduce the external conduction and radiation
interference of the AC drive.
'HFUHDVHWKHFRQGXFWLRQLQWHUIHUHQFHÀRZLQJIURPWKH
power supply to the AC drive and improve the anti-
interference capacity of the AC drive.
DC
reactor
MD series AC drive
of 7.5G and above
FRQ¿JXUHGZLWK'&
reactor as standard
Improve the power factor of the input side.
,PSURYHWKHHI¿FLHQF\DQGWKHUPDOVWDELOLW\RIWKH$&GULYH
Eliminate the impact of higher harmonics of the AC
drive input side and reduce the external conduction
and radiation interference.
AC output
reactor
Between AC drive
output side and the
motor, close to the
AC drive
The output side of the AC drive generally has much
KLJKHUKDUPRQLFV:KHQWKHPRWRULVIDUIURPWKH$&
drive, there is much distributed capacitance in the circuit
and certain harmonics may cause resonance in the
circuit, bringing about the following two impacts:
Degrade the motor insulation performance and
damage the motor in the long run.
Generate large leakage current and cause frequent AC
drive protection trips.
If the distance between the AC drive and the motor is
greater than 100 m, install an AC output reactor.
1) Do not install the capacitor or surge suppressor on the output side of the AC drive.
2WKHUZLVH LW PD\ FDXVH IDXOWV WR WKH$& GULYH RU GDPDJH WR WKH FDSDFLWRU DQG VXUJH
suppressor.
,QSXWV2XWSXWVPDLQFLUFXLWRIWKH$&GULYHFRQWDLQKDUPRQLFVZKLFKPD\LQWHUIHUHZLWK
the communication device connected to the AC drive. Therefore, install an anti-interference
¿OWHUWRPLQLPL]HWKHLQWHUIHUHQFH
3) For more details on peripheral devices, refer to related selection in chapter 8.
efesotomasyon.com
Содержание MD380 Series
Страница 8: ...efesotomasyon com...
Страница 9: ...1 Safety Information and Precautions efesotomasyon com...
Страница 16: ...Safety Information and Precautions MD380 User Manual 16 efesotomasyon com...
Страница 17: ...2 Product Information efesotomasyon com...
Страница 28: ...Product Information MD380 User Manual 28 efesotomasyon com...
Страница 29: ...3 Mechanical and Electrical Installation efesotomasyon com...
Страница 46: ...Mechanical and Electrical Installation MD380 User Manual 46 efesotomasyon com...
Страница 47: ...4 Operation Display and Application Examples efesotomasyon com...
Страница 82: ...Operation Display and Application Examples MD380 User Manual 82 efesotomasyon com...
Страница 83: ...5 Function Code Table efesotomasyon com...
Страница 138: ...Function Code Table MD380 User Manual 138 efesotomasyon com...
Страница 139: ...6 Description of Function Codes efesotomasyon com...
Страница 249: ...7 EMC efesotomasyon com...
Страница 261: ...8 Selection and Dimensions efesotomasyon com...
Страница 293: ...9 Maintenance and Troubleshooting efesotomasyon com...