Description of Function Codes
MD380 User Manual
- 156 -
Function Code
Parameter Name
Setting Range
Default
F2-06
Vector control slip gain
50%–200%
100%
)RU6)9&LWLVXVHGWRDGMXVWVSHHGVWDELOLW\DFFXUDF\RIWKHPRWRU:KHQWKHPRWRUZLWK
load runs at a very low speed, increase the value of this parameter; when the motor with
load runs at a very large speed, decrease the value of this parameter.
For CLVC, it is used to adjust the output current of the AC drive with same load.
Function Code
Parameter Name
Setting Range
Default
F2-07
69&WRUTXH¿OWHUWLPHFRQVWDQW
1–31
28
Function Code
Parameter Name
Setting Range
Default
F2-09
Torque upper limit source in
speed control mode
0: F2-10
1: AI1
2: AI2
3: AI3
4: Pulse reference (DI5)
5: Communication reference
0
F2-10
Digital setting of torque upper
limit in speed control mode
0.0%–200.0%
150.0%
In the speed control mode, the maximum output torque of the AC drive is restricted by F2-
09. If the torque upper limit is analog, pulse or communication setting, 100% of the setting
corresponds to the value of F2-10, and 100% of the value of F2-10 corresponds to the AC
drive rated torque.
For details on the AI1, AI2 and AI3 setting, see the description of the AI curves in group F4.
For details on the pulse setting, see the description of F4-28 to F4-32.
:KHQWKH$&GULYHLVLQFRPPXQLFDWLRQZLWKWKHPDVWHULI)LVVHWWR³FRPPXQLFDWLRQ
VHWWLQJ´)³'LJLWDOVHWWLQJRIWRUTXHXSSHUOLPLWLQVSHHGFRQWUROPRGH´FDQEHVHWYLD
communication from the master.
In other conditions, the host computer writes data -100.00% to 100.00% by the
communication address 0x1000, where 100.0% corresponds to the value of F2-10. The
FRPPXQLFDWLRQSURWRFROFDQEH0RGEXV&$1RSHQ&$1OLQNRU352),%86'3
Function Code
Parameter Name
Setting Range
Default
F2-13
Excitation adjustment proportional gain
0–20000
2000
F2-14
Excitation adjustment integral gain
0–20000
1300
F2-15
Torque adjustment proportional gain
0–20000
2000
F2-16
Torque adjustment integral gain
0–20000
1300
These are current loop PI parameters for vector control. These parameters are automatically
REWDLQHGWKURXJK$V\QFKURQRXVPRWRUFRPSOHWHDXWRWXQLQJDQGQHHGQRWEHPRGL¿HG
The dimension of the current loop integral regulator is integral gain rather than integral time.
Note that too large current loop PI gain may lead to oscillation of the entire control loop.
Therefore, when current oscillation or torque fluctuation is great, manually decrease the
proportional gain or integral gain here.
efesotomasyon.com
Содержание MD380 Series
Страница 8: ...efesotomasyon com...
Страница 9: ...1 Safety Information and Precautions efesotomasyon com...
Страница 16: ...Safety Information and Precautions MD380 User Manual 16 efesotomasyon com...
Страница 17: ...2 Product Information efesotomasyon com...
Страница 28: ...Product Information MD380 User Manual 28 efesotomasyon com...
Страница 29: ...3 Mechanical and Electrical Installation efesotomasyon com...
Страница 46: ...Mechanical and Electrical Installation MD380 User Manual 46 efesotomasyon com...
Страница 47: ...4 Operation Display and Application Examples efesotomasyon com...
Страница 82: ...Operation Display and Application Examples MD380 User Manual 82 efesotomasyon com...
Страница 83: ...5 Function Code Table efesotomasyon com...
Страница 138: ...Function Code Table MD380 User Manual 138 efesotomasyon com...
Страница 139: ...6 Description of Function Codes efesotomasyon com...
Страница 249: ...7 EMC efesotomasyon com...
Страница 261: ...8 Selection and Dimensions efesotomasyon com...
Страница 293: ...9 Maintenance and Troubleshooting efesotomasyon com...