Chapter 4 Parameter Description
42
When the tension increase terminal is active, the tension controlled by
the inverter will be increased according to the parameter.
FH-58
line
speed
setting
source
0: AI1 setting
1: AI2 setting
2: AI3 setting
3: pulse setting
4: communication setting
1
0
It is relevant to the situation when FH-00 is set as 4 (line speed control
mode). For details, please refer to the description of FH-00.
FH-59
taper compensation
correction
1mm~10000mm
1mm
0
It is the auxiliary parameter for tension taper control. For details, please
refer to the description of FH-09.
FH-60
tension taper
effectiveness
selection for
close loop
tension control
0: taper effective
1: taper ineffective
1
0
This function code decides whether the tension taper will be effective
upon close loop tension control.
In general, when the control adopts roll feedback, it is unnecessary for
the tension taper to have influence over the roll setting position (PID
reference). However, it will be effective on the external taper output
because it is used for the control proportion valve to adjust the tension.
Input/output selection: when the inverter is the tension control
inverter, the following functions are the supplementary for the