Chapter 4 Parameter Description
35
failure will be reported by the inverter after material supply interrupt is
detected.
FH-37: When it is set as 0, the material supply interrupt auto detection
function is inactive.
FH-38: Only when the line speed is higher than the value can the
material supply interrupt be detected.
FH-39: Only when the abnormal change of the curling radius exceeds
this range can the material supply interrupt be detected.
FH-40: Only when the lasting time of the abnormal change of the
curling radius exceeds this delay can the material supply interrupt be
detected.
When the above three conditions are satisfied simultaneously, the
inverter reports ERR24 (material supply interrupt failure)
4.6 PID parameters
This group of parameters is only related to the close loop speed
mode.
FH-41
proportiona
l gain 2
0.0s~100.0s
0.1
20.0
FH-42
integral
time I2
0.01s~10.00s
0.01s
2.00s
FH-43
differential
time D2
0.000s~1.000s
0.001s
0.000s
This is the second group of parameters. FA-05, FA-06 and FA-07
belong to the first group of PID parameters. Best result can be achieved
in different conditions by setting the two groups of parameters.