Reverse Sequence Order
: Checking this box will cause the power on
sequence to run in reverse order with output channel 12 on first, ending
with output 1, when the
Enable All Outputs
button is pressed on the
Status
& Control
page.
Network Watchdog:
Select a Watchdog to edit
: Select one of the six independent Watchdogs to
configure. Each Watchdog, if enabled, will cause the unit to periodically ping
up to two remote IP addresses to verify the network connection status. If
there is no response from either address the unit will cycle the power on all
outputs that are configured in the
Cycle Outputs
setting below. This feature
is useful for re-booting a modem or other network device that is powered by
one of the distribution panel outputs, to help recover the network IP
connection when one of these devices has crashed. A delay time must be
entered in the
Sequence/Cycle Delay
field for this function to work. Power
for a cycled channel will be held in the off state for the duration set by the
Sequence/Cycle delay time, then will be turned back on.
Watchdog Enabled
: Check this box to enable the selected Watchdog.
Primary IP Address
: Enter the remote IP address you would like the selected
Watchdog to monitor. If left blank the unit will monitor the Gateway IP
address listed in the Network Setup page.
Secondary IP Address
: Enter an optional second IP address that the unit can
monitor to verify network status. The Network Watchdog will only trigger if
both the Primary and Secondary IP addresses fail to respond.
Cycle Outputs
: This sets which output(s) to power cycle when the Network
Watchdog triggers.
Watchdog Timeout
: Enter the time (1 to 80 minutes) that the remote IP
address must stop responding to ping requests from the panel, before the
Network Watchdog will trigger an output power cycle. Ensure this time is
greater than the normal start-up time for the network hardware to prevent
nuisance power cycle events at system start up.
Maximum Cycle Attempts:
This setting will limit the maximum number of
times the panel can attempt to cycle power to the output(s) before giving
up, if the remote IP address continues to be unresponsive. Set Maximum
Cycle Attempts to zero for no limit.
Data Logging:
Data Logging rate:
Enable this feature to keep a running record the system
voltage, system current, channel output currents, fuse status, and alarm