INSTALLATION
INSTALLATION
2.1 Unit placement
Position of device must be established by the system design-
er or other qualified professional and must take into account
both technical requirements and any local laws in force.
The Filomuro incasso fancoil has to be installed only in
high position on the wall, with a maximum height of 2,2
m (except for use in cooling only).
Avoid installing the unit near:
• areas exposed to direct sunlight
• heat sources, except for solar radiations filtered by glass
• wet rooms and areas with probable contact with water
• rooms with oil vapors
• rooms subject to high frequencies
Make sure that:
• the wall on which you intend to install the unit has an ap-
propriate structure and capacity
• the wall surface is not crossed by pipelines or power lines
• the surface is perfectly levelled
• there are no obstructions nearby that could compromise
the inlet and outlet airflow
• the installation position is suitable to allow condensate
drain outside the
• the installation position is optimal to avoid that the airflow
is directed towards people
2.2 Installation mode
The assembly steps described below and their drawings refer
to a version of the machine with connections on the right
side.
For ideal installation and performance levels, carefully fol-
low the instructions in the manual.
Failure to do so may cause system malfunctions and auto-
matically voids the warranty, and relieves the constructor
of any harm caused to person, animals or property.
2.3 Installation minimum distances
The figure shows the minimum installation distances of the
unit.
It is important to ensure that the air flow is not occluded
by walls or obstacles.
20 mm
20 mm
120 mm