Innova Innova Filomuro Incasso SLWI Скачать руководство пользователя страница 27

27

 

INSTALLATION

 General  start-up

Before the activation:

Make sure that the remote control is connected to the 
mains.

In case of a master switch on the power supply line, switch 
on the system by inserting the switch.

To activate the device

– 

press the 

 key

he symbol 

 lights up

3.4    Main  functions

 Operating mode set-up

to switch the operating mode

– 

press the 

 key for about 2 seconds

The symbol 

 on indicates the Heating function enable

The symbol 

 on indicate the Cooling function enable

In heating function the symbols is alight with setpoint 
higher than the room temperature.

In cooling function the symbols is alight with setpoint 
lower than the room temperature.

When the setpoint is incorrect both symbols are switched 

off.

 Put in stand-by the control

To put in stand-by the control

– 

press the 

 key for about 2 seconds

The control goes out

In stand-by mode the control ensures an antifreeze safety. 
In case of temperature <5 °C, the hot water solenoid valve 
outputs and boiler consent are activated automatically.

 Set room temperature 

To set-up the temperature 

– 

operate the 

 

 keys to decrease or increase the desired value

The displayed value change

The adjustment range goes from 16 to 28 °C, with a reso-

lution of 0,5 °C.

Out of range values from 5 °C and 40 °C are allowed, ex-
cept in automatic mode. These value should be set only 
for short periods of time.

 Automatic  operation

To select the Automatic function

– 

press the 

 key for about 2 seconds

The symbol   on indicates the Automatic function enable

The ventilation speed is automatically adjusted between 

a minimum value and a maximum value based on an al-

gorithm type PI, according to the actual distance from the 
room temperature set-point.

 Silent  operation

To select the Silent operation

– 

press the 

 key for about 2 seconds

The symbol 

 on indicates the Silent function enable

The ventilation speed is limited at a more reduced maxi-

mum value.

 Night  function

To select the Night function

– 

press the 

 key for about 2 seconds

The symbol 

 on indicate the Night function enable

The ventilation speed is limited at a very low value.

The set temperature changes automatically:

Содержание Innova Filomuro Incasso SLWI

Страница 1: ...EN Installation and user manual SLWI...

Страница 2: ...he personnel that the operation described could cause electrocution if not performed according to the safety rules High heating danger Signals to the personnel that the operation described could cause...

Страница 3: ...device to an other owner or relocate it to other premises If the manual gets damaged or lost download a copy from the website All repair or maintenance interventions must be per formed by the technic...

Страница 4: ...hnical data Models m u 400 600 800 Coil water content L 0 50 0 61 0 77 Maximum working pressure bar 10 10 10 Maximum water inlet temperature C 80 80 80 Minimum water inlet temperature C 4 4 4 Hydrauli...

Страница 5: ...ns and weight for shopping Filomuro Filomuro Filomuro Models m u 400 600 800 Dimensions and weight for shopping Total length mm 1020 1220 1320 Total height mm 490 490 490 Total depth mm 213 213 213 We...

Страница 6: ...not crossed by pipelines or power lines the surface is perfectly levelled there are no obstructions nearby that could compromise the inlet and outlet airflow the installation position is suitable to...

Страница 7: ...lines L H P 2 5 Installation Make sure that the support wall is suitable for weight of the appliance Make sure that the wall is not crossed by pipelines load bearing construction elements or power lin...

Страница 8: ...of the plaster holder mesh levelled with the finished wall A Plaster holder mesh B Skimming C Aesthetic panel attachment holes A B C Make sure that the metal casing does not deform during installation...

Страница 9: ...screws not supplied check the right fixing check right alignment It is necessary for right functioning of the device that during the whole installation phase the working space remains clean Regularly...

Страница 10: ...hetic panel closer to the form work check the right alignment of the front panel with the flap on the unit if necessary move the appliance on the brack ets for correct alignment secure the hinges usin...

Страница 11: ...ize in accordance with good installation practices and the applicable law Keep in mind that undersized pipelines lead to poor sys tem operation and or a loss of thermal and cooling per formance Positi...

Страница 12: ...unit comes without any shut off valve In other case depending of the request the unit can be sup plied with valves already assembled or supplied separately to be mounted during installation The 2 way...

Страница 13: ...ting for water inlet pipe D water outlet pipe fitting E electrical cable entry hole A D E B C Connection with 3 way diverting valve unit with thermoelectric actuator V30688 In case of choice for the 3...

Страница 14: ...a slope never less than 1 insulate fitting points Pay attention to the tilt of the condensate drain pipe Make the condensate liquid flow directly onto a gutter or into a white water drain Make a sipho...

Страница 15: ...adapted to the absorption of the apparatus considering also any oth er devices in parallel operation the power supply voltage and system frequency match to the values indicated on the device s plate d...

Страница 16: ...ing diagram of the unit you are installing You can use a cable embedded in the wall in the position traced with the installation template to make the electrical connection recommended connection for d...

Страница 17: ...Serial connection for wall mounted remote control respect the AB polarization H2 Hot water temperature probe 10 k M1 Fan motor DC Inverter Y1 Water solenoid valve 230 V 50 Hz 1 A power output L N 230...

Страница 18: ...the cables unscrew the corresponding screw with a screwdriver remove the conductor When the CP contact opens connected to a clean contact not live the unit is in stand by The display reads CP Error si...

Страница 19: ...speed 1 100 rpm V3 Minimum fan speed 680 rpm V4 Super silent speed 400 rpm E Heating cooling selection input Y1 Water solenoid valve 230 V 50 Hz 1 A power output M1 Fan motor DC Inverter TA 3 speed ro...

Страница 20: ...nds provided with water probe the on board H2 probe will not be connected the device will be controlled from the remote command If this is not the case connect the 10 k probe located inside the batter...

Страница 21: ...0V00 Printed circuit board for 0 10 V interface The PCB is included in the supply L N 230 V 50 Hz electrical power supply 10V Device pilot input 0 10 V Input impedance 25 k Y1 Water solenoid valve 23...

Страница 22: ...value 1400 rmp for voltage values 1 1 V 10 V DC The solenoid valve Y1 is enabled by voltage values 1 V DC turns off with values 0 9 V DC Error signals LED signals LED off The input signal is below 0...

Страница 23: ...in one of the fan coils connected to it Mounting The wall mounted remote control must be installed on internal walls at a height of about 1 5 m from the floor away from doors or windows away from heat...

Страница 24: ...ic wires through the hole provided fix the base of the control to the wall using suitable screw and plugs perform the electrical connection close the control Pay attention not to crush the conductors...

Страница 25: ...nsor enabling badge remote change of season Function When the contact connected to the CP input is closed all the users connected will be switched off At the touch of a button on the display the symbo...

Страница 26: ...ed to the pressure of any key Display A Display area A Statuses and active alarms on display Supervision on Flashing with CP closed contact Switched on for alarm indication Resistance enabled indicati...

Страница 27: ...utputs and boiler consent are activated automatically Set room temperature To set up the temperature operate the keys to decrease or increase the desired value The displayed value change The adjustmen...

Страница 28: ...the key to decrease the value wait 20 seconds After 20 seconds from the last action the panel brightness will be reduced to increase the comfort during night use On the display will appear only the ro...

Страница 29: ...99 max increase or decrease the value with the icons The displayed value change Enable or disable Wifi select the menu item uu by pressing The default value appears select YS to enable wifi select rs...

Страница 30: ...ings Factory reset select the menu item Fr by pressing The default value appears select YS to reset the settings select no to keep the current settings ProbeT regulation offset room temperature probe...

Страница 31: ...LL MOUNTED CONTROL B3V151 B3V152 4 1 Electric connections Connection diagram B3V151 1 PCB 2 Wall control H2 N276660C DATA I O LED H4 H2 2 1 SM B3V152 1 PCB 2 Built in wall control H2 N276660C DATA I O...

Страница 32: ...upply by placing the main switch of the system on OFF Warnings Do not lean on the fancoil to avoid damaging the appli ance Do not manually move the horizontal louver of the air out let Always use the...

Страница 33: ...leaning A Vacuum cleaner B Long nozzle C Filter C B A To clean the filters to use a vacuum cleaner to aspirate dust A Running water B Filter B A wash the filter with running water allow it dry Do not...

Страница 34: ...t energy sav ing keep the filters clean keep the doors and windows of the locations fitted with air conditioning systems closed as much as possible During summer limit the entry of direct sun rays int...

Страница 35: ...you were to turn on the problem may be in the electronic control The ventilation motor is jammed or burnt Check the motor windings and check if the fan rotates freely The wirings are not correct Chec...

Страница 36: ...realized by Innova technical dept INNOVA S r l Via I Maggio 8 38089 Storo TN ITALY tel 39 0465 670104 fax 39 0465 674965 info innovaenergie com N420310A Rev 01...

Отзывы: