17
INSTALLATION
2.10 Diagrams and configurations electrical controls
Remote control EDA649 - EDB649 / EWG649 - EWW649 (code suffix-0P00)
Printed circuit broad with continuous
modulation for wall control connection
The PCB is included in the supply.
-AB+
Serial connection for wall-mounted remote control (respect the AB polarization)
H2
Hot water temperature probe 10 kΩ
M1
Fan motor DC Inverter
Y1
Water solenoid valve (230 V/50 Hz 1 A power output)
L-N
230 V/50 Hz electrical power supply connection
BO
Boiler consent output (free contact max 1 A)
CH
Chiller consent output (free contact max 1 A)
CP
Presence sensor input (if closed, the fancoil goes into stand-by)
AIR
Optional air probe
SM
H2 AIR
N540022B
Содержание Innova Filomuro Incasso SLWI