19
INSTALLATION
Wall mounted remote control EDA649 - EDB647 / EWG649 - EWW649
The control panel is to be ordered separately.
A
Terminal blocks
A
The terminal blocks for the connection of the wall-mounted
controller accept:
• rigid or flexible wires with a 0.2 to 1 mm² cross-section
• rigid or flexible wires with 0.75 mm² cross-section if two
wires are connected to the same terminal block
• rigid or flexible wires with 0,75 mm² cross-section If the
wires have wire end ferrules with a plastic collar
To connect the cables:
– strip 8 mm of the wire
– if the wire is rigid, you can insert it easily whereas
– if it is flexible, it is advisable to use long nose pliers
– push the wire completely in
– check that it is anchored by pulling it gently
A
Terminal blocks
A
+ A B -
To disconnect the cables:
– unscrew the corresponding screw with a screwdriver
– remove the conductor
When the CP contact opens, connected to a clean contact
not live, the unit is in stand-by. The display reads "CP".
Error signals
The PCB is fitted with a LED, thanks to which it is possible to
intuit the operating status.
LED signals
–
LED off
Device switched off or without power supply
–
LED on
Normal operating of the device
–
LED 1 flash / pause
Water temperature probe H2 alarm not suitable, temporary stop of the ventilation until the temperature reaches an appropriate
value *
–
LED 2 flashes / pause
Motor alarm (for example jamming due to foreign bodies or fault in the rotation sensor)
–
LED 3 flashes / pause
Water probe alarm disconnected or faulty
–
LED 6 flashes / pause
Communication error with the wall remote control. In case of a non-communication for more than 5 minutes the device is deac-
tivated.
* In case of a operation without water probe H2, the fan stop thresholds will be ignored.