INSTALLATION
2�8 Condensate drain
The unit is complete of a drain pan that collects the con-
densate fluid that is produced during cooling operation and
must be conveyed to a suitable place for unloading.
1�
drain connection, Ø 14 mm
A
Connection to the condensate drain
A
drain connection
B
the drainage tube
A
B
– connect a rubber drainage tube
– direct it to a suitable place for unloading
A
Filomuro
B
liquid drain pipe
A
B
– provide a slope never less than 1%
– insulate fitting points
Pay attention to the tilt of the condensate drain pipe.
Make the condensate liquid flow directly onto a gutter or
into a "white water" drain
Make a siphon to prevent bad smells returning up the
pipe towards the room. The curve of the siphon must be
lower than the condensation collection bowl.
Install a pump if the drain pipe has to pass a gradient that
hinders the flow.
Check
After the installation is completed:
– pour the water very slowly into the condensate drain pan
– check the correct outflow