Inner Range Inception Security Controller
Installation Manual. Rev. 4.0
© 2016 - 2020. Inner Range Pty Ltd.
3
www.innerrange.com
Important Notes.
1. Earthing.
When using the supplied 24V PSU, Inception “0V” connections are connected to mains
earth. To avoid earth loops, ensure that all “0V” terminals on the controller, all LAN and
UniBus Modules and peripherals connected to these Modules are NOT connected to an
earth lug, the metal enclosure or any other earth connection.
Connecting 0V to Earth may create earth loops.
2. Installer User name, Password and PIN Code.
The Default User name/password for web access is installer/installer.
The Default Installer PIN Code is 01. These credentials must all be changed by the
Installer as soon as possible. i.e. As soon as commissioning commences. Note that a
timed lockout is applied after 3 failed login attempts to the web interface.
3. Sirens.
The Inception controller does not provide dedicated siren outputs for 8 Ohm horn speakers.
If connecting a siren to the controller, a piezo screamer or a siren device that includes a
built-in driver circuit must be connected to one of the 4 relay outputs. e.g. CSD-1003/CSD-
1008 screamers or CSD-1000/CSD-1004 Speaker/Siren combo units.
See
“Output Relays
(OUT1-
4)” in the ‘WIRING DIAGRAMS’ section of this manual.
Two dedicated outputs for 8
Ohm horn type siren speakers are provided on 8 Zone LAN Expander Modules.
4. End-of-line (EOL) Resistors.
The inputs on the Inception controller and expansion modules utilize dual end-of-line
resistors. The default EOL scheme uses 2k2 & 2k2 or 2k2 & 6k8 resistors. 4 alternate
EOL schemes are shown under “Zone Inputs” in the ‘WIRING’ section.
If Inception is replacing an existing system and the existing detectors are wired with a
single EOL scheme or a dual EOL scheme that is not supported, the EOL resistors in the
detectors will need to be changed.
See the schematic diagram and examples
under “Zone Inputs” in the ‘WIRING DIAGRAMS’
section of this manual.
5. Reporting.
Inception does not provide an on-board dialer port for alarm reporting via PSTN.
Alarm reporting is currently provided by one of two methods:
a) SkyTunnel reporting. Built-in reporting via an internet connection.
b) T4000 Multipath-IP communicator. Multiple redundant 3G reporting paths in addition to
internet reporting.
S
ee ‘Alarm Reporting’ in this manual for details.
6. LAN Expansion.
Expansion modules connected to the Inception controller via the RS485 system LAN, must
be connected using appropriate twisted-pair cable.
If Inception is replacing another product, any existing LAN wiring may only be used if it
meets the LAN cabling requirements described
in the ‘LAN & Reader Ports’ section of this
manual.
7. Release Notes.
Inception Release Notes are published for every firmware release. Always read the latest
Release Notes for information on changes and enhancements.