Zone Inputs.
Eight zone inputs are provided to allow monitoring of detection devices, door reeds, etc.
The default EOL configuration is 2k2+2k2 or 2k2+6k8 (shown in the schematic diagram below).
A different configuration may be selected. Current options are:
1k+1k (Seal=1k / Alarm=2k)
6k8+3k3 (Seal=6k8 / Alarm=10k1)
4k7+4k7 or 4k7+2k2 (Seal=4k7 / Alarm=9k4 or 6k9)
10k+10k (Seal=10k / Alarm=20k)
Example: PIR movement detector.
Example: Reed Switch.
Tamper Input.
Detector terminals may be arranged
& labelled differently to this
example. Please check the
manufacturer’s documentation.
For tamper switches provided with the recommended
enclosures, select “Open Circuit Secure” in the
Controller hardware settings in the browser.