Review Events
&/or time
scheduling is
wrong or appears
out of order.
•
Date & Time Settings
are incorrect
•
The time has been
manually set or the
configured NTP server is
not configured correctly.
Navigate to the Date & Time configuration page.
In order to set the time manually, clic
k “Set
Date/Time Manually”.
Once the dialog box appears either set the time
using the calendar or by clicki
ng the “Get time
from browser“. This will sync the inception
panel
’s time to that of the device being used to
setup the system.
The input states
are backwards
(active when it
should be secure
& vice-versa).
End-of-Line Resistors are
incorrectly wired, or the
active contact is Normally
Open.
Configure the Input as normal.
Navigate to the Inputs configuration page, select
the input &
enable the “Swap Active & Secure
States”.