Installation and programming manual
48
Wiring diagram of an intrusion-control panel
Caption
• All resistors @ 15K
• Normally-open keyswitch contact
• Sounder/Flasher activated by "positive removed"
• Device must be Earthed (see terminal 12)
Input programming:
IO1-IO2
Type: Delayed
Balance: DEOL
Events 1, 2, 4, 5, 6, and 8 switch output 4 ON
Events 3 and 7 switch output 4 OFF
IO3
Balance: EOL
Events 9, 11 and 12 switch output 4 ON
Event 10 switches output 4 OFF
Outputs programming:
IO4
Type: Bistable
Polarity: normally open
IO5
Already programmed by the selected parameter
Enable intrusion control
The diagram illustrates an application with:
• Two DEOL zones for:
- Connect two detectors (e.g. PIRs, magnetic contacts, etc.).
- Device alarm and tamper must refer to the same input
• One balanced tamper zone for:
- external sounder/flasher tamper detection;
- frontplate removal detection.
• One alarm output, where the open-collector output controls a single
polarity changeover relay for:
- self-powered external sounder/flasher command;
- internal sounder/flasher command;
• keyswitch input to arm/disarm intrusion control panel.