Installation and programming manual
18
Installation
Chapter 7
Installation
7.1
Installation instructions
1.
Pull the connection cables through the cable entry, ensure that they do
not obstruct operations.
2.
Using the wall-mount screws, attach the backplate to the wall.
Danger:
Care must be taken not to drill in the vicinity of electrical
wiring, heating ducts and plumbing.
3.
Complete the connections as indicated in paragraph
7.2 Connections
.
4.
Connect the two wires coming from the external power source or the
optional IPS12015DT to terminals 1 and 2 (+PWR and -PWR).
5.
Connect the battery (12V-1.2Ah) to the Red wire (1) and Black (2)
(table on page 12, ‘[E]’) and locate it in its housing.
Attention:
Be sure the polarity is correct.
6.
Connect the serial cable and carry out the programming process using
the SmartLeague software. On completion of the programming process,
remove the serial cable.
7.
Using the screws (supplied), secure the frontplate in place. Be sure that
the battery is not in the way of the screws.
8.
On first power up, the device will perform self-diagnosis. If no anomalies
are detected, the device will start to operate normally. The green LED
will go On to indicate that the device is operating normally.
If anomalies are detected, the red LED will signal them as shown in the
table in paragraph
5.2 LED
.