background image

8

Device description

Power supply stations

Chapter 2

DEVICE DESCRIPTION

2-1

Inside the box

The package contains the SmartLevel power supply station with its components:

metal enclosure with the following devices, already mounted and connected:

•• SmartLevel mother board (IN088)

•• Switching power supply

•• LIVPWR100 board (IN140)

•• thermal probe

•• tamper-protection device

Installation manual (this manual)

Plastic bag with:

•• backup-battery wire

•• earth connection ring terminal

The backup battery is not included in the package.

2-2

Functions and features

POWER OUTPUTS 

GRADE 3

The grade 3 ancillary outputs are available on the LIVPWR100 board and are:

+AUX1

 

+AUX2

 

+AUX3

 

Each output is independent and is monitored and protected by a protection circuit.

In the event of overvoltage, short-circuit or overload, the circuit will block the

power supply which will be restored only after the cause of the problem has been

removed.

POWER OUTPUTS 

WITH GRADE 2 OR 

LOWER SECURITY 

RATING

The ancillary power outputs with grade 2 or lower security rating, each protected

by a resettable fuse in case of current requirements of over 1.35A, are available

on the motherboard and are:

+AUX1

 

+AUX3

 

Hotmelt fuses, unlike filament fuses, interrupt the power supply when current

absorption exceeds the allowed threshold. Once the cause of excessive current

absorption has been removed, the hotmelt fuse will restore the normal power

supply without need for component replacement.

SIGNALLING 

OUTPUTS

The signalling outputs are available on the motherboard and are:

NO

NC

 and 

COM

 terminals of the relay output activate in the event of open

enclosure or enclosure dislodgement tamper.

OC1

, output that will be activated in the event of primary power source failure

(Mains)

OC2

, output that will be activated in the event of disconnected or inefficient

battery

T6

, output that will be activated in the event of current dispersion to earth

T7

T8

T9

 outputs that will signal faults relating to power outputs with grade

3 security rating (AUX1, 2, 3 on the LIVPWR100 board)

••

T7

, output that will signal the intervention of a protection device of one of 

the protected outputs AUX1, 2, 3

Содержание SmartLevel Series

Страница 1: ...1 Installation and Programming manual SmartLevel Power supply stations Installation and programming manual EN 50131 1 EN 50131 6 EN 50130 4 EN 50130 5 ...

Страница 2: ... at its option repair or replace any defective products Improper use that is use for purposes other than those mentioned in this manual will void the warranty Contact Our authorized dealer or visit our website for further information regarding this warranty Limited warranty INIM Electronics s r l shall not be liable to the purchaser or any other person for damage arising from improper storage hand...

Страница 3: ...nd use 6 1 4 The system parts 7 Chapter 2 Device description 8 2 1 Inside the box 8 2 2 Functions and features 8 2 3 Description and technical specifications 9 Chapter 3 Installation 12 3 1 Wall mounting 12 3 2 Connecting the Mains power supply 12 3 3 Connecting the backup battery 13 Chapter 4 Using the device 15 4 1 Powering devices 15 4 2 Relay Output 16 4 3 OC1 and OC2 16 4 4 Tx terminal output...

Страница 4: ...4 Power supply stations ...

Страница 5: ...nd knowledge of the laws and bylaws regarding service conditions and the prevention of accidents are able to identify and avoid all possible situations of danger 0 2 Graphic conventions Following are the graphic conventions used in this manual Note The detached notes contain important information about the text ATTENTION The Attention prompts indicate that total or partial disregard of the procedu...

Страница 6: ...nternal 12V 5 0A switching power supply and housing for 12V 17Ah battery COMPLIANCY EN 50131 1 2006 A1 2009 EN 50131 6 2008 EN 50130 4 2011 EN 50130 5 2011 Certifying body IMQ S p A Security rating 3 1 3 Application and use The SmartLevel power station is an optional part of the intrusion control system which is capable of supplying 12V power to the remote loads of the system The power station sup...

Страница 7: ...E This is the module which starting from the voltage value 230V 50Hz supplied by the mains network it is connected to supplies the SmartLevel motherboard and the LIVPWR100 board with the nominal voltage stabilized at 12V measured voltage value 13 8V required to power the installation and recharge the batteries The power supply module is housed beside the board and is certified EN50131 6 compliant ...

Страница 8: ... ancillary power outputs with grade 2 or lower security rating each protected by a resettable fuse in case of current requirements of over 1 35A are available on the motherboard and are AUX1 AUX3 Hotmelt fuses unlike filament fuses interrupt the power supply when current absorption exceeds the allowed threshold Once the cause of excessive current absorption has been removed the hotmelt fuse will r...

Страница 9: ...LIVPWR100 board IN140 35mA 13 8V Maximum deliverable current for external loads security grade 2 system 12 hour autonomy 500mA 1 35A security grade 3 system 30 hour autonomy 130mA 450mA Maximum deliverable current on each AUX terminal mother board IN088 1 35A LIVPWR100 board IN140 2A Threshold for overload protection 15 4V SD low voltage 11V Fault voltage on power outputs 9 8V Threshold for deep d...

Страница 10: ...on terminal board to mains 230V F Mains cable entry G Ground connection screws H Frontplate earth wire I Wires between switching power supply and station J Thermal probe K Anchor screw locations for the metal backbox L Dislodgement tamper M Compartment for backup battery B C E H A F SPS12060XG3 D I J L M G I K K K K B C E H A F SPS12160XG3 D I J K L M G K K K ...

Страница 11: ... Ancillary power supply 37 AUX3 14 OC1 Open collector output 15 OC2 28 T6 Output terminal 30 T7 32 T8 34 T9 36 T10 17 29 31 33 35 Power supply negative earth or GND Table 5 LIVPWR100 board terminal board n icon identifier description 1 2 3 4 D S Not used 5 AUX1 12V Ancillary power supply 7 AUX2 9 AUX3 6 8 10 Power supply negative earth or GND Table 6 Power supplies IPS12060G IPS12160G A Mains inpu...

Страница 12: ...should be easily accessible The distance between contacts must be at least 3mm The manufacturer strongly advises the use of a magnetothermic switch with C intervention curve and nominal maximum current 16A The protective earthing system must be compliant with all safety standards and laws in force ATTENTION Ensure that the Mains is switched Off during the mains connection phase Danger of electric ...

Страница 13: ...ave HB flame rating or higher Using the battery wire B included connect the battery directly to the control panel motherboard ATTENTION Ensure that battery polarity is correct black wire negative red wire positive Connect the cable to the control panel using the appropriate connector on the switching power supply C table 6 D The lead battery is the secondary power source which powers the system wh...

Страница 14: ...ry temperature The thermal probe protects against battery overheating and consequent permanent damage to the battery It is supplied and inserted in the connector on the power supply unit D table 6 C Using adhesive insulating tape attach the thermal probe to the battery E in such way as to provide optimized heat transfer measurements A B D E C SPS12060XG3 SPS12060XG3 A B D E C B ...

Страница 15: ...artLevel station is used to power the devices of an installation with grade 3 security rating the AUXx outputs on the LIVPWR100 board must be used table 5 LIVPWR100 board terminal board If the SmartLevel is used to power the peripherals connected to the I BUS of the SmartLiving intrusion control panel the connection must be completed as follows If an isolator is required on the I BUS line IB100RU ...

Страница 16: ...its terminal is floating During standby status the terminal closes to ground The OC1 output activates in the event of mains failure primary power source The OC2 output activates in the event of battery trouble disconnected or inefficient Both outputs reset to standby closed to ground when their respective activation causes cease 4 4 Tx terminal outputs The T6 T7 T8 T9 and T10 outputs are open coll...

Страница 17: ...an occur in the event of Loss of communication between the SmartLevel motherboard and the LIVPWR100 board Loss of communication between the LIVPWR100 board and the power supply unit The T10 outputs signals a fault caused by the total loss of operating capacity of the SmartLevel motherboard 4 5 Connection to intrusion control systems Compliance with standard EN50131 6 grade 3 provides the following...

Страница 18: ...18 Using the device Power supply stations ...

Страница 19: ...ctrical and electronic waste disposal centers In alternative to independent management the equipment to be discarded can be taken to the dealer upon purchase of a similar new device Electronic devices sized under 25 cm can be taken to electronic product dealers with at least 400 m2 store surface free of charge without any purchase obligation Suitable collection for subsequent recycling processing ...

Страница 20: ...tations Centobuchi via Dei Lavoratori 10 63076 Monteprandone AP ITALY Tel 39 0735 705007 _ Fax 39 0735 704912 info inim biz _ www inim biz ISO 9001 Quality Management certified by BSI with certificate number FM530352 ...

Отзывы: