![INIM Electronics SmartLevel Series Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/inim-electronics/smartlevel-series/smartlevel-series_installation-and-programming-manual_2061483007.webp)
General information
7
Installation and programming manual
1-4
The system parts
SMARTLEVEL
MOTHER BOARD
This is the board which, starting from the nominal voltage stabilized at 12V
,
supplies the voltage to the power outputs it is equipped with, which have grade 2
or lower security rating.
The board communicates over the I-BUS line with the LIVPWR100 board in order
to monitor its operating status and the status of the power supply module. In the
event of malfunction it enables or restores the appropriate signalling outputs.
The board also communicates via the RS232 serial line with the PC it receives
firmware upgrades from.
LIVPWR100 BOARD
This is the board which, starting from the nominal voltage stabilized at 12V
,
supplies the voltage to the grade 3 power outputs it is equipped with. It also
manages the monitoring of the grade 3 power outputs and the activation of their
protection devices.
The board communicates with the power supply module in order to monitor its
operating status.
POWER SUPPLY
MODULE
This is the module which, starting from the voltage value (230V~, 50Hz) supplied
by the mains network it is connected to, supplies the SmartLevel motherboard and
the LIVPWR100 board with the nominal voltage stabilized at 12V
(measured
voltage value: 13.8V) required to power the installation and recharge the
batteries.
The power-supply module is housed beside the board and is certified EN50131-6
compliant.
The mains current (230V~) is the primary power source of the system. Refer also
to
paragraph 3-2 Connecting the Mains power supply
.
BATTERY
The secondary power-source of the system. The power station casing houses a
lead battery (12V 7Ah or 12Ah, depending on the model). The power station
monitors the battery status (efficiency and charge). A fault signal will be
generated if inefficient battery conditions are detected. If primary (230V~) power
failure occurs, the battery will take over automatically. Refer also to
paragraph 3-
3 Connecting the backup battery
.
THERMAL PROBE
This wire must be connected to the station and attached to the battery pack. This
device monitors the temperature of the external battery pack and regulates the
battery charge accordingly. Refer also to
paragraph 3-3 Connecting the backup
battery
.
Содержание SmartLevel Series
Страница 4: ...4 Power supply stations ...
Страница 18: ...18 Using the device Power supply stations ...