Table 13.
Diagnostic Objects Sorted by Object Name (continued)
Object
Identifier
Binary Input
Object Name
Description
Notification
Class
When Exists
BI 296
Diagnostic: Design Min Position at
Minimum Fan Speed Fail
Diagnostic: Design Min Position at
Minimum Fan Speed Fail
004 –
Information
With RTVM
installed
BI 294
Diagnostic: Design Min Position Setpoint
Fail
Diagnostic: Design Min Position Setpoint
Fail
004 –
Information
With RTEM
installed
BI 76
Diagnostic: Dirty Filter
Diagnostic: Dirty Filter
003 – Advisory
Always
BI 289
Diagnostic: Discharge Air Heat Setpoint
Failure
Diagnostic: Discharge Air Heat Setpoint
Failure
004 –
Information
With RTOM
installed
BI 264
Diagnostic: Economizer Actuator Fault
Diagnostic: Economizer Actuator Fault
004 –
Information
Always
BI 107
Diagnostic: Entering Evap Temp Sensor
Fail
Diagnostic: Entering Evap Temp Sensor
Fail
002 – Service
Required
Always
BI 295
Diagnostic: Enthalpy Setpoint Fail
Diagnostic: Enthalpy Setpoint Fail
004 –
Information
Always
BI 40
Diagnostic: Exhaust Fan Proving Failure
Diagnostic: Exhaust Fan Proving Failure
001 – Critical
With RTEM
installed
BI 288
Diagnostic: Exhaust Fan Setpoint Failure
Diagnostic: Exhaust Fan Setpoint Failure
004 –
Information
With RTOM
installed
BI 151
Diagnostic: External Auto-Stop
Diagnostic: External Auto-Stop
004 –
Information
With RTOM
installed
BI 307
Diagnostic: Excessive Air
Diagnostic: Excessive Air
004 -
Information
With RTRM 16
or higher
installed
BI 39
Diagnostic: Fan Failure
Diagnostic: Fan Failure
001 – Critical
With RTEM
installed
BI 259
Diagnostic: Flame Rollout Switch Open
Diagnostic: Flame Rollout Switch Open
004 –
Information
With Gas Heat
installed
BI 262
Diagnostic: Flame Sensed with Gas Valve
Off
Diagnostic: Flame Sensed with Gas
Valve Off
004 –
Information
With Gas Heat
installed
BI 256
Diagnostic: Freezestat Tripped
Diagnostic: Freezestat Tripped
004 –
Information
With RTOM
installed
BI 247
Diagnostic: FroStat Trip
Diagnostic: FroStat Trip
004 –
Information
With RTOM
installed
BI 263
Diagnostic: Gas Heat Module Failure
Diagnostic: Gas Heat Module Failure
004 –
Information
Always
BI 312
Diagnostic: Gas Heat Supply Airflow Limit
Trip
Diagnostic: Gas Heat Supply Airflow
Limit Trip
004 -
Information
Always
BI 51
Diagnostic: Heat Failure
Diagnostic: Heat Failure
003 – Advisory
Always
BI 258
Diagnostic: Heating High Temp Limit
Open
Diagnostic: Heating High Temp Limit
Open
004 –
Information
With Gas Heat
installed
BI 290
Diagnostic: IGN1 Communications Timed
out
Diagnostic: IGN1 Communications
Timed out
004 –
Information
With Gas Heat
installed
BI 291
Diagnostic: IGN2 Communications Timed
out
Diagnostic: IGN2 Communications
Timed out
004 –
Information
With Gas Heat
installed
BI 260
Diagnostic: Inducer Proving Switch Fail
Diagnostic: Inducer Proving Switch Fail
004 –
Information
With Gas Heat
installed
BI 34
Diagnostic: Local Cool Setpoint Fail
Diagnostic: Local Cool Setpoint Fail
002 – Service
Required
Always
BI 38
Diagnostic: Local Emergency Stop
Initiated
Diagnostic: Local Emergency Stop
Initiated
001 – Critical