Table 11.
All Object Types Sorted by Object Name (
Refer to previous tables for detailed descriptions of objects
)
(continued)
Object
Identifier
Object Name
Description
When Exists
BI 22
Economizer Airside Enable Status
Indicates the status of the airside economizer system
With RTEM installed
BO 7
Economizer Minimum Position Enable
Command
Command the unit to the minimum position
operation
With RTEM installed
AO 1
Economizer Minimum Position Setpoint
BAS
BAS supplied economizer position minimum setpoint
value
With RTEM installed
AI 86
Economizer Minimum Position Setpoint
Local
Indicates the local economizer minimum position
setpoint
With RTEM installed
MI 44
Economizer System Status
Indicates the operating state of the waterside
economizer system
Always
AO 42
Economizing Enthalpy Enable Setpoint
Enthalpy Setpoint below which economizing can be
used
With RTEM installed
AO 41
Economizing Temperature Enable
Setpoint
Temperature Setpoint below which economizing can
be used
With RTEM installed
MO 2
Emergency Override Command
Command the unit into an emergency mode of
operation
Always
AI 9
Exhaust Damper Position Status
Indicates the unit exhaust damper position
Always
AI 71
Exhaust Enable Damper Position Setpoint
Status
Exhaust air damper minimum position to enable
exhaust sequence
With RTEM installed
MI 39
Exhaust Fan Proving Status
Indicates if the unit exhaust fan is off or on.
With RTOM installed
(Only activates with
RTEM installed)
AI 8
Exhaust Fan Speed Command
Indicates the unit commanded exhaust fan speed.
With RTEM installed
MI 38
Exhaust Fan Status
Indicates the commanded state of the exhaust fan.
With RTEM installed
AO 33
Exhaust or Return Fan Configuration
Sets the equipment exhaust or return fan type.
Always
AI 90
Exhaust or Return Fan Type
Describes the different exhaust or return fan types:
1 = None
2 = 1-Speed Exhaust Fan
7 = 1-Speed Exhaust Fan with Modulating Exhaust
Damper
Always
AI 6
Filter Runtime Hours
Indicates the number of hours air has flowed through
the filter.
Always
AV 1
Filter Runtime Hours Setpoint
The setpoint value used by the filter run hours
calculation.
Always
BO 13
Filter Timer Reset
Command the unit to reset the accumulated filter run
hours.
Always
AO 20
Heat Capacity Enable Setpoint BAS
BAS supplied heating demand limit capacity setpoint
value.
With all heat types
MO 8
Heat Cool Mode Request BAS
Command the unit to a specific application mode.
Always
BO 5
Heat Lockout Command
Command the unit to prevent heating operation.
Always
MI 29
Heat Output 1
Indicates the commanded state of heating output 1.
Always
MI 30
Heat Output 2
Indicates the commanded state of heating output 2.
Always
MI 31
Heat Output 3
Indicates the commanded state of heating output 3.
Always
MI 32
Heat Output 4
Indicates the commanded state of heating output 4.
Always
AI 2
Heat Primary Capacity Status
Indicates the unit primary heating capacity being
utilized.
With modulating heat