28
BAS-SVP09F-EN
Table 3.
Analog Output (continued)
Object
Identifi-
er
Object Name
Description
Units of
Measure
IP/SI
Valid Range (F°)
Refresh Rate
(Sec.)
When
Exists
AO 11
Space Temperature
BAS
BAS supplied space
air temperature
sensor value
Fahrenheit
Celsius
-40.0 to 150.0
-40.0 to 65.6
900
Always
AO 14
Outdoor Air
Temperature BAS
BAS supplied
outdoor air
temperature sensor
value
Fahrenheit
Celsius
-40.0 to 158.0
-40.0 to 70.0
900
Always
AO 15
Outdoor Air Humidity
BAS
BAS supplied
outdoor air humidity
sensor value
Percent
0 to 100
900
Always
AO 16
Outdoor Air Minimum
Flow Setpoint BAS
BAS supplied
minimum outdoor
airflow setpoint
0 CFM = 0 l/s
(litres/second)
40000 CFM =
18878 l/s
0 to 40,000
NA
With RTVM
version 3 or
greater
installed
and RTRM
firmware 9
or greater
installed
AO 18
Space CO
2
Concentration BAS
BAS supplied space
CO
2
sensor value
Part-per-million
mg/kg
0.0 to 2000
900
Always
AO 19
Cool Capacity Enable
Setpoint BAS
BAS supplied cooling
demand limit
capacity setpoint
value
Percent
0 to 100
NA
Always
AO 20
Heat Capacity Enable
Setpoint BAS
BAS supplied
heating demand
limit capacity
setpoint value
Percent
0 to 100
NA
With all
heat types
AO 21
Space
Dehumidification
Setpoint BAS
BAS supplied space
dehumidification
setpoint value
Percent
40 to 65
NA
With RTDM
installed
AO 23
Discharge Air Reheat
Setpoint BAS
BAS supplied
discharge air reheat
setpoint value
Fahrenheit
Celsius
65.0 to 80.0
18.3 to 26.7
NA
With RTDM
installed
AO 25
Space Humidity BAS
BAS supplied space
humidity sensor
value
Percent
10 to 100
900
With RTDM
installed
AO 29
Occupied Offset
Offset used to
calculate setpoints in
occupied mode
Fahrenheit
Celsius
1.0 to 5.0
0.6 to 2.8
NA
Always
AO 30
Standby Offset
Offset value used to
calculate setpoints in
standby mode
Fahrenheit
Celsius
1.0 to 10.0
0.06 to 5.6
NA
Always
AO 31
Unoccupied Cooling
Setpoint
Cooling temperature
setpoint used or
control in
unoccupied mode.
Fahrenheit
Celsius
50 to 90
10.0 to 32.2
NA
Always
AO 32
Unoccupied Heating
Setpoint
Heating temperature
setpoint used for
control in
unoccupied mode
Fahrenheit
Celsius
50.0 to 90.0
10.0 to 32.2
NA
Always
AO 33
Exhaust or Return Fan
Configuration
Sets the equipment
exhaust or return
fan type
NA
1.0 to 255
NA
Always
AO 34
Power Exhaust Enable
Setpoint BAS
BAS supplied power
exhaust enabled
setpoint value
Percent
0.0 to 100
NA
With RTEM
installed