BAS-SVP09F-EN
33
Table 4.
Analog Input (continued)
Object
Identifi-
er
Object Name
Description
Units of Measure
IP/SI
When Exists
AI 108
Tracer TD5 Major
Version
Major Software version number of the TD5 module
NA
With TD5 installed and
RTRM version 15 or
higher installed
AI 109
Tracer TD5 Minor
Version
Minor Software version number of the TD5 module
NA
With TD5 installed and
RTRM version 15 or
higher installed
Table 5. Analog Value
Object Identifier
Object Name
Description
Units
Valid Range
AV 1
Filter Runtime Hours Setpoint
The setpoint value used by the
filter run hours calculation.
Hours
0 to 10,000
Table 6. Multistate Output
BCI-R
Object
Identifier
Object Name
Description
Object States
*not all states apply to all
equipment
When Exists
MO 1
Economizer Airside
Enable BAS
Command the state of the airside
economizer system
1 = Disabled
2 = Enabled
3 = Auto
With RTEM Installed
MO 2
Emergency Override
Command
Command the unit into an
emergency mode of operation
1 = Normal
2 = Pressurize
3 = Depressurize
4 = Purge
5 = Shutdown
6 = Fire
Always
MO 7
Occupancy Request
Command the unit into an
occupancy mode.
1 = Occupied
2= Unoccupied
3 = Occupied Bypass
4 = Occupied Standby
Always
MO 8
Heat Cool Mode
Request BAS
Command the unit to a specific
application mode.
1 = Auto
2 = Heat
3 = Morning Warmup
4 = Cool
5 = Night Purge
6 = Precool
7 = Off
8 = Test
9 = Emergency Heat
10 = Fan Only
11 = Free Cool
12 = Ice Making
13 = Max Heat
14 = Economy Mode
15 = Dehumidifying
16 = Calibrate
Always