BAS-SVP09F-EN
29
Table 3.
Analog Output (continued)
Object
Identifi-
er
Object Name
Description
Units of
Measure
IP/SI
Valid Range (F°)
Refresh Rate
(Sec.)
When
Exists
AO 35
Space Cooling Setpoint
High Limit BAS
High limit value to
clamp the space
cooling setpoint
Fahrenheit
Celsius
50.0 to 90.0
10.0 to 32.2
NA
Always
AO 36
Space Cooling Setpoint
Low Limit BAS
Low limit value to
clamp the space
cooling setpoint
Fahrenheit
Celsius
50.0 to 90.0
10.0 to 32.2
NA
Always
AO 37
Space Heating Setpoint
High Limit BAS
High limit value to
clamp the space
heating setpoint
Fahrenheit
Celsius
50.0 to 90.0
10.0 to 32.2
NA
Always
AO 38
Space Heating Setpoint
Low Limit BAS
Low limit value to
clamp the space
heating setpoint
Fahrenheit
Celsius
50.0 to 90.0
10.0 to 32.2
NA
Always
AO 41
Economizing
Temperature Enable
Setpoint
Temperature
setpoint below which
economizing can be
used
Fahrenheit
Celsius
50.0-140.0
10.0-60.0
NA
With RTEM
installed
AO 42
Economizing Enthalpy
Enable Setpoint
Enthalpy setpoint
below which
economizing can be
used
Btu per lb
19.0-28.0
NA
With RTEM
installed
AO 43
Daytime Warmup
Initiate Temperature
Setpoint BAS
BAS supplied
daytime warmup
Initiate temperature
setpoint
Fahrenheit
50.0 to 87.0
NA
RTAM is
present
and heat is
present
AO 44
Supply Fan Minimum
Speed BAS
BAS supplied
minimum fan speed
Percent
0.0 to 100.0
NA
Supply fan
is not
single
speed
AO 45
Supply Fan Maximum
Speed BAS
BAS supplied
maximum fan speed
Percent
0.0 to 100.0
NA
Supply fan
is not
single
speed
AO 46
Outdoor Air
Temperature Heating
Lockout Low Limit
Temperature at
which Mechanical
Heating will be
locked out on a Heat
Pump
Fahrenheit
0.0 to 45.0
NA
Configured
as a Heat
Pump
Table 4.
Analog Input
Object
Identifi-
er
Object Name
Description
Units of Measure
IP/SI
When Exists
AI 1
Cooling Capacity
Status
Indicates the unit cooling capacity being utilized
Percent
Always
AI 2
Heat Primary Capacity
Status
Indicates the unit primary heating capacity being
utilized
Percent
With modulating heat
AI 3
Heat Secondary
Capacity Status
Indicates the unit secondary heating capacity being
utilized
Percent
With RTDM installed
AI 5
Reheat Capacity Status
Indicates the unit reheat heating capacity being
utilized
Percent
With RTDM installed
AI 6
Filter Runtime Hours
Indicates the number of hours air has flowed
through the filter
Hours
Always
AI 7
Supply Fan Speed
Command
Indicates the unit commanded supply fan speed
Percent
Always